Loss-of-Potential, CCVT Transient Detection,
4-25
Load-Encroachment, and Directional Element Logic
SEL-311B Instruction Manual
50QFP—Forward Directional Negative-Sequence Current Pickup
50QRP—Reverse Directional Negative-Sequence Current Pickup
Setting Range:
0.25–5.00 A secondary (5 A nominal phase current inputs, IA, IB, IC)
0.05–1.00 A secondary (1 A nominal phase current inputs, IA, IB, IC)
The 50QFP setting (3I
2
current value) is the pickup for the forward fault detector 50QF of the
negative-sequence voltage-polarized directional elements (see Figure 4.6). Ideally, the setting is
above normal load unbalance and below the lowest expected negative-sequence current
magnitude for unbalanced forward faults.
The 50QRP setting (3I
2
current value) is the pickup for the reverse fault detector 50QR of the
negative-sequence voltage-polarized directional elements (see Figure 4.6). Ideally, the setting is
above normal load unbalance and below the lowest expected negative-sequence current
magnitude for unbalanced reverse faults.
50QFP and 50QRP Set Automatically
If configuration setting E32 = AUTO, settings 50QFP and 50QRP are set automatically at:
50QFP = 0.50 A secondary (5 A nominal phase current inputs, IA, IB, IC)
50QRP = 0.25 A secondary (5 A nominal phase current inputs, IA, IB, IC)
50QFP = 0.10 A secondary (1 A nominal phase current inputs, IA, IB, IC)
50QRP = 0.05 A secondary (1 A nominal phase current inputs, IA, IB, IC)
a2—Positive-Sequence Current Restraint Factor, I
2
/I
1
Setting Range:
0.02–0.50 (unitless)
Refer to Figure 4.6.
The a2 factor increases the security of the negative-sequence voltage-polarized directional
elements. It keeps the elements from operating for negative-sequence current (system
unbalance), which circulates due to line asymmetries, CT saturation during three-phase faults, etc.
a2 Set Automatically
If configuration setting E32 = AUTO, setting a2 is set automatically at:
a2 = 0.1
For setting a2 = 0.1, the negative-sequence current (I
2
) magnitude has to be greater than 1/10 of
the positive-sequence current (I
1
) magnitude in order for the negative-sequence voltage-polarized
directional elements to be enabled (
1
2
I
•
1
.
0
I
>
).
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......