S
ETTINGS
S
HEET
Page 8
OF
22
FOR THE
SEL-311B R
ELAY
Date
R
ELAY
S
ETTINGS
(S
ERIAL
P
ORT
C
OMMAND
SET
AND
F
RONT
P
ANEL
)
Date Code 20011205
Reset time from reclose cycle (0.00–999999.00 cycles in 0.25-cycle steps)
79RSD =
Reset time from lockout (0.00–999999.00 cycles in 0.25-cycle steps)
79RSLD =
Reclose supervision time limit (OFF, 0.00–999999.00 cycles in 0.25-cycle
steps) (set 79CLSD = 0.00 for most applications; see Figure 6.2)
79CLSD =
Switch-Onto-Fault (See Figure 5.3)
(Make the following settings if preceding enable setting ESOTF = Y.)
Close enable time delay (OFF, 0.00–16000.00 cycles in 0.25-cycle steps)
CLOEND =
52A enable time delay (OFF, 0.00–16000.00 cycles in 0.25-cycle steps)
52AEND =
SOTF duration (0.50–16000.00 cycles in 0.25-cycle steps)
SOTFD =
Zone 1 Extension Scheme Settings (See Figure 3.11)
(Make the following settings if preceding enable setting EZ1EXT = Y.)
Zone 1 extension delay time (0.00–16000.00 cycles)
Z1EXTD =
Zone 1 distance multiplier (1.00–4.00)
Z1EXTM =
Demand Metering Settings (See Figures 8.11 and 8.13)
(Make the following settings, whether preceding enable setting EDEM = THM or ROL.)
Time constant (5, 10, 15, 30, 60 minutes)
DMTC =
Phase pickup (OFF, 0.50–16.00 A secondary {5 A nom.};
0.10–3.20 A secondary {1 A nom.})
PDEMP =
Residual ground pickup (OFF, 0.50–16.00 A secondary {5 A nom.};
0.10–3.20 A secondary {1 A nom.})
GDEMP =
Negative-sequence pickup (OFF, 0.50–16.00 A secondary {5 A nom.};
0.10–3.20 A secondary {1 A nom.})
QDEMP =
Other Settings
Minimum trip duration time (4.00–16000.00 cycles in 0.25-cycle steps)
(see Figure 5.1)
TDURD =
Close failure time delay (OFF, 0.00-16000.00 cycles in 0.25-cycle steps)
(see Figure 6.1)
CFD =
Three-pole open time delay (0.00–60.00 cycles in 0.25-cycle steps)
(usually set for no more than a cycle; see Figure 5.3)
3POD =
Open pole option (52, 27)
OPO =
Three-pole open undervoltage (0.0–150.0 V secondary)
27PO =
Load detection phase pickup (OFF, 0.25–100.00A{5 A nom.};
0.05–20.00 A {1 A nom.}) (see Figure 5.3)
50LP =
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......