Date Code 20011205
Application Settings for SEL-221 Series Relays
14-51
SEL-311B Instruction Manual
SEL-221-16
TO
SEL-311B S
ETTINGS
C
ONVERSION
G
UIDE
Set APP = 221-16 in the SEL-311B to configure the relay to closely approximate the features,
performance, and settings of an SEL-221-16. When APP = 221-16, the SEL-311B:
1. Configures itself as a phase and ground distance relay with ground directional
overcurrent elements, and reclosing functions.
2. Configures contact inputs and outputs to emulate those in an SEL-221-16.
3. Presents the user only with those settings associated with SEL-221-16 type features.
4. Automatically calculates all other settings required to simulate an SEL-221-16.
If additional capability is needed (e.g., M
IRRORED
B
ITS
or SEL
OGIC
control equations) the relay
may be returned to the setting APP = 311B to make all of the SEL-311B settings visible. It is
important to remember that changing from APP = 311B to APP = 221-16 changes settings in the
relay. Changing from APP = 221-16 to APP = 311B makes more SEL-311B settings visible, but
does not change any other settings. If SEL-311B functions are used after setting APP is changed
from 221-16 to 311B, do not change setting APP back to 221-16.
As described above, when setting APP = 221-16, the user is presented only with SEL-311B
settings associated with the features found in an SEL-221-16. This section explains how to make
those remaining SEL-311B settings directly from the settings used in an SEL-221-16.
There are mainly two kinds of settings in the SEL-311B, relay settings and SEL
OGIC
settings.
Relay settings are settings for protective elements. SEL
OGIC
settings are Boolean expressions
used to customize the logic of the SEL-311B. To set the SEL-311B to emulate an SEL-221-16,
follow these four steps:
1. Turn on the SEL-221-16 application setting by making setting APP = 221-16. See
Application Settings
below.
2. Convert the appropriate SEL-221-16 settings to SEL-311B settings using the simple
equations shown in Table 14.16. Be sure to convert from primary quantities
(SEL-221-16 settings) to secondary quantities (SEL-311B settings). See
Convert
SEL-221-16 Primary Quantities to SEL-311B Secondary Quantities
below.
3. For each Mask Logic setting in the SEL-221-16 shown in Table 14.17, create an
equivalent SEL
OGIC
control equation using the logical OR of each Relay Word bit
(Table 14.18) asserted in the mask.
4. Test the relay to verify intended performance.
The remainder of this section shows how to perform steps 1 through 3 above, and also gives an
example of step 3.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......