9-18
Setting the Relay
Date Code 20011205
SEL----311B Instruction Manual
Row
Bit
Definition
Primary
Application
25
M3P
Zone 3 phase distance, instantaneous (see
Figure 3.6)
Tripping,
Control
M3PT
Zone 3 phase distance, time delayed (see
Figure 3.12)
Z3G
Zone 3 mho and/or quad. distance, instantaneous
(see Figure 3.9)
Z3GT
Zone 3 ground distance, time delayed (see
Figure 3.12)
*
*
*
*
26
Z3T
Zone 3 phase and/or ground distance, time delayed
(see Figure 3.12)
*
50P2
Level 2 Phase instantaneous overcurrent element
(A, B, or C) above pickup setting 50P2P; see
Figure 3.13)
67P2
Level 2 torque controlled phase instantaneous
overcurrent element (derived from 50P2; see
Figure 3.13)
67P2T
Level 2 phase definite-time overcurrent element
67P2T timed out (derived from 67P2; see
Figure 3.13)
50P3
Level 3 Phase instantaneous overcurrent element
(A, B, or C) above pickup setting 50P3P; see
Figure 3.13)
67P3
Level 3 torque controlled phase instantaneous
overcurrent element (derived from 50P3; see
Figure 3.13)
67P3T
Level 3 phase definite-time overcurrent element
67P3T timed out (derived from 67P3; see
Figure 3.13)
27
50G2
Level 2 residual ground instantaneous overcurrent
element (residual ground current above pickup
setting 50G2P; see Figure 3.16)
67G2
Level 2 torque controlled residual ground
instantaneous overcurrent element (derived from
50G2; see Figure 3.16)
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......