![Schweitzer Engineering Laboratories SEL-311B Instruction Manual Download Page 602](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-311b/sel-311b_instruction-manual_1216695602.webp)
2
Command Summary
Date Code 20011205
SEL-311B Instruction Manual
STA
Show relay self-test status.
SUM
Show newest event summary.
SUM A
Acknowledge oldest even summary.
SUM N
View oldest unacknowledged event report.
SUM N [A]
Display or acknowledge event summary number “N”.
TAR R
Reset the front-panel tripping targets.
TAR
n k
Display Relay Word row. If
n
= 0 through 51, display row n. If
n
is an element name (e.g., 50P1) display
the row containing element n. Enter
k
for repeat count.
TIM
Show or set time (24 hour time). Show time presently in the relay by entering just TIM. Example time
22:47:36 is entered with command TIM 22:47:36.
TRI
Trigger an event report.
Access
Level B
Commands
Access Level B commands primarily allow the user to operate output contacts. All Access Level 1
commands can also be executed from Access Level B. The screen prompt is: ==>
BRE
n
Enter BRE W to preload breaker wear. Enter BRE R to reset breaker monitor data.
CLO
Close the circuit breaker. See the Note in the
Set Close
discussion, following Figure 6.1 for more
information concerning the CLO command.
GRO
n
Change active group to Group
n
.
OPE
Open the circuit breaker. See the Note following Figure 5.2 and the Note in the
Lockout State
discussion,
following Table 6.1, for more information concerning the OPE command.
PUL
n k
Pulse output contact n (OUT101 - OUT107, ALARM) for
k
(1 - 30) seconds. Parameter
n
must be
specified;
k
defaults to 1 if not specified.
Access
Level 2
Commands
The Access Level 2 commands allow unlimited access to relay settings, parameters, and output contacts.
All Access Level 1 and Access Level B commands are available from Access Level 2. The screen prompt
is: =>>
CON
n
Control Remote Bit RB
n
(Remote Bit
n
;
n
= 1 through 8). Execute CON
n
and the relay responds:
CONTROL RB
n
. Then reply with one of the following:
SRB
n
set Remote Bit
n
(assert RB
n
).
CRB
n
clear Remote Bit
n
(deassert RB
n
).
PRB
n
pulse Remote Bit
n
(assert RB
n
for 1/4 cycle).
COP
m n
Copy relay and logic settings from Group
m
to Group
n
.
LOO Set
M
IRRORED
B
ITS
port to loopback.
PAS
Show existing Access Level 1, B, and 2 passwords.
PAS 1 xxxxxx
Change Access Level 1 password to xxxxxx.
PAS B xxxxxx
Change Access Level B password to xxxxxx.
PAS 2 xxxxxx
Change Access Level 2 password to xxxxxx.
SET
n
Change relay settings (overcurrent, reclosing, timers, etc.) for Group
n
.
SET L
n
Change
SEL
OGIC
control equation settings for Group
n
.
SET G
Change global settings.
SET P
n
Change
Port
n
settings.
SET R
Change Sequential Events Recorder (SER) settings.
SET T
Change text label settings.
STA C
Resets self-test warnings/failures and reboots relay.
VER
Displays version and configuration information.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......