14-58
Application Settings for SEL-221 Series Relays
Date Code 20011205
SEL-311B Instruction Manual
Default Contact Input Functions
311 Input
221-16 Label
Function
IN101
IN1
Monitor
IN102
PT
Monitor
IN103
BT
Monitor
IN104
DC
Monitor
IN105
52A
Circuit Breaker Aux. Contact
IN106
ET
External Event Report Trigger
Default Output Contact Logic Equations
OUT101 = TRIP
OUT102 = TRIP
OUT103 = CLOSE
OUT104 = 0
(Reserved for MA1)
OUT105 = 0
(Reserved for MA2)
OUT106 = M1P + Z1G + M2PT + Z2GT + 67G1
(Reserved for MA3)
OUT107 = Z3T + 51GT
(Reserved for MA4)