![Schweitzer Engineering Laboratories SEL-311B Instruction Manual Download Page 321](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-311b/sel-311b_instruction-manual_1216695321.webp)
Date Code 20011205
Serial Port Communications and Commands
10-15
SEL-311B Instruction Manual
COM Command (Communication Data)
The
COM
command displays integral relay-to-relay (M
IRRORED
B
ITS
) communications
performance data. For more information on M
IRRORED
B
ITS
, see
Appendix I: M
IRRORED
B
ITS
.
To get a summary report, enter the
COM
command with the channel parameter (A or B).
=>COM A <ENTER>
COM A <ENTER>
COM A <ENTER>
COM A <ENTER>
SEL-311B Date: 08/22/00 Time: 16:24:01.623
EXAMPLE: BUS B, BREAKER 3
FID=SEL-311B-R100-V0-Z001001-D20000818 CID=F30B
Summary for Mirrored Bits channel A
For 08/18/00 18:36:09.279 to 08/21/00 18:36:11.746
Total failures 1 Last error Relay Disabled
Relay Disabled 1
Data error 0 Longest Failure 2.458 sec.
Re-Sync 0
Underrun 0 Unavailability 0.996200
Overrun 0
Parity error 0
Framing error 0 Loopback 0
Bad Re-Sync 0
=>
If only one M
IRRORED
B
ITS
port is enabled, the channel specifier may be omitted. Use the L
parameter to get a summary report, followed by a listing of the COMM records.
=>COM L <ENTER>
COM L <ENTER>
COM L <ENTER>
COM L <ENTER>
SEL-311B Date: 08/22/00 Time: 16:24:01.623
EXAMPLE: BUS B, BREAKER 3
FID=SEL-311B-R100-V0-Z001001-D20000818 CID=F30B
Summary for Mirrored Bits channel A
For 08/18/00 17:18:12.993 to 08/21/00 18:37:36.123
Total failures 4 Last error Relay Disabled
Relay Disabled 2
Data error 0 Longest Failure 2.835 sec.
Re-Sync 0
Underrun 1 Unavailability 0.000003
Overrun 0
Parity error 1
Framing error 0 Loopback 0
Bad Re-Sync 0
Failure Recovery
# Date Time Date Time Duration Cause
1 08/18/00 18:36:09.279 08/18/00 18:37:36.114 2.835 Relay Disabled
2 08/19/00 13:18:09.236 08/19/00 13:18:09.736 0.499 Parity error
3 08/20/00 11:43:35.547 08/20/00 11:43:35.637 0.089 Underrun
4 08/21/00 17:18:12.993 08/21/00 17:18:13.115 0.121 Relay Disabled
=>
There may be up to 255 records in the extended report. To limit the number of COMM records
displayed in the report to the 10 most recent records, type
COM 10 L <ENTER>
. To select
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......