3-40
Distance, Overcurrent, Voltage,
Date Code 20011205
and Synchronism Check Elements
SEL-311B Instruction Manual
Synchronism Check Elements Voltage Inputs
The two synchronism check elements use voltage inputs V
P
and V
S
for both elements:
V
P
Phase input voltage (V
A
, V
B
, V
C
, V
AB
, V
BC
, or V
CA
), designated by setting SYNCP
(e.g., if SYNCP = VB, then V
P
= V
B
)
V
S
Synchronism check voltage, from SEL-311B Relay rear-panel voltage input VS
For example, if V
P
is designated as phase input voltage V
B
(setting SYNCP = VB), then
rear-panel voltage input VS is connected to B-phase on the other side of the circuit breaker. The
voltage across terminals VB-N is synchronism checked with the voltage across terminals VS-NS
(see Figure 1.2 and Figures 2.4 and 2.5).
System Frequencies Determined from Voltages V
A
and V
S
To determine slip frequency, you need to determine the system frequencies on both sides of the
circuit breaker. Voltage V
S
determines the frequency on one side. Voltage V
A
determines the
frequency on the other side.
Synchronism Check Elements Operation
Refer to Figure 3.24 and Figure 3.25.
Voltage Window
Refer to Figure 3.24.
Single-phase voltage inputs V
P
and V
S
are compared to a voltage window, to verify that the
voltages are “healthy” and lie within settable voltage limits 25VLO and 25VHI. If both voltages
are within the voltage window, the following Relay Word bits assert:
59VP indicates that voltage V
P
is within voltage window setting limits 25VLO and 25VHI
59VS indicates that voltage V
S
is within voltage window setting limits 25VLO and 25VHI
As discussed previously, voltage V
A
determines the frequency on the voltage V
P
side of the
circuit breaker. Voltage V
A
is also compared against voltage limits 25VLO and 25VHI to assure
“healthy voltage” for frequency determination, with corresponding Relay Word bit output 59VA.
If V
P
is a phase-to-phase voltage, V
A
is multiplied internally by
Ö
3 for the 25VLO and 25VHI
checks.
Other Uses for Voltage Window Elements
If voltage limits 25VLO and 25VHI are applicable to other control schemes, Relay Word bits
59VP, 59VS, and 59VA can be used in other logic at the same time they are used in the
synchronism check logic.
If synchronism check is not being used, Relay Word bits 59VP, 59VS, and 59VA can still be used
in other logic, with voltage limit settings 25VLO and 25VHI set as desired. Enable the
synchronism check logic (setting E25 = Y) and make settings 25VLO and 25VHI. Apply Relay
Word bits 59VP, 59VS, and 59VA in the desired logic scheme, using SEL
OGIC
control equations.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......