Date Code 20011205
Inputs, Outputs, Timers, and Other Control Logic
7-25
SEL-311B Instruction Manual
Figure
7.20: Active Setting Group Switching (with Single Input) Time Line
Active Setting Group Switching Example 2
Previous SEL relays (e.g., SEL-321 and SEL-251 Relays) have multiple settings groups
controlled by the assertion of three optoisolated inputs (e.g., IN101, IN102, and IN103) in
different combinations as shown in Table
Table
7.6: Active Setting Group Switching Input Logic
Input States
Active
IN103 IN102 IN101
Setting
Group
0 0 0
Remote
0 0 1
Group
1
0 1 0
Group
2
0 1 1
Group
3
1 0 0
Group
4
1 0 1
Group
5
1 1 0
Group
6
The SEL-311B Relay can be programmed to operate similarly. Use three optoisolated inputs to
switch between the six setting groups in the SEL-311B Relay. In this example, optoisolated