BERMAD 

Fire Protection

Strainers

Approvals

Typical Applications

■ 

Water spray systems

■ 

Deluge systems

■ 

Fire monitors

■ 

Automatic sprinkler systems

■ 

Foam proportioner/generator provided in the water line

■ 

Upstream of Pressure Control valves

■ 

Upstream of a Sensitive System Devices

Options

Consult BERMAD for other Materials of Construction  
or other available specifications.

The BERMAD FP-60F-D/DV Basket Strainers are 
intended to be installed in fire protection pipelines 
primarily to prevent the clogging of fire sprinkler 
nozzles and other debris sensitve components in 
water or foam fire systems.

The BERMAD FP-60F-D/DV is designed for in-line 
maintenance available with a large diameter flushing 
outlet for easy screen cleaning and simple screen 
basket extraction, requiring only cover removal.

The ratio of the FP-60F-D/DV strainer’s basket screen 
area to the inlet pipe area is more than 10:1, ensuring 
continued system performance, a low pressure drop 
and longer intervals between cleaning.

NFPA 11, 13, 15 and 16 standards state that listed strainers 
shall be provided in the main pipeline of all systems 
using nozzles where the water is likely to contain 
obstructive material. 

Features and Benefits

■ 

UL-Listed and ULC size

 for Fire systems 

■ 

Low pressure drop

 – Safety and reliability, ensures firewater 

availability

■ 

Easy in-line maintenance

 – Large diameter flushing valve 

for fast and easy interim cleaning

■ 

Suitable to prevent clogging

 – Nozzles, sprinklers or 

other types of fire system discharge outlets. Designed 
to trap foreign material of 3.2mm (

1

/

8

") diameter or larger

■ 

Large screen basket

 – Large basket area, Increasing 

system reliability and safety

■ 

Suitable for installation in varied orientations

 - Refer to 

installation and maintenance section 

■ 

Compatible for use with corrosive fluids and harsh 
environments

 – High Build Epoxy coated body/cover 

and stainless steel 316 screen

■ 

Suitable for Foam Systems

 – For use with foam 

proportioners or foam generators in compliance with 
NFPA 11 requirements.

UL-Listed 3" through to 16" 
Strainers, Pipeline (HLCV)

ULC Certified for Canada 3" through to 16" 
Strainers, Pipeline (HLCV7)

Fire Line Basket Strainer  
with Flushing Drain 

Model FP-60F-D/DV

Model FP-60F-D/DV

Model FP-60F-DV 

(14 & 16")

Model FP-60F-D 

(14 & 16")

VdS

(in process)

VdS

(in process)

Model FP-60F-D

Model FP-60F-DV

Summary of Contents for FP-60F-D

Page 1: ...sted strainers shall be provided in the main pipeline of all systems using nozzles where the water is likely to contain obstructive material Features and Benefits UL Listed and ULC size for Fire systems Low pressure drop Safety and reliability ensures firewater availability Easy in line maintenance Large diameter flushing valve for fast and easy interim cleaning Suitable to prevent clogging Nozzle...

Page 2: ... area ratio of 10 1 shall be used with foam proportioners or foam generators and should be installed in the water pipeline upstream of the water control valve The NFPA 13 15 and 16 standards stipulate that a Listed Strainer shall be provided in the main pipeline of all systems utilizing nozzles with waterways less than 3 8 9 5 mm and for any system where the water is likely to contain obstructive ...

Page 3: ...ll as the dynamic loads It is recommended to install a differential pressure gauge rooted to upstream and downstream of the FP 60F D DV strainer in order to show the degree of strainer blockage The maximum allowable differential pressure across the strainer is 7 psi or 0 5 bar at maximum system flow Placing In Service Verify that all strainer cover bolts are well tightened close the drain plug and...

Page 4: ...isassembly of any strainer component The strainer basket screen should be cleaned after each system operation or flow test and during routine inspections as follows For strainers fitted with a flushing valve 1 Fully open the flushing drain valve for at least 5 seconds or until the flushed water becomes visibly clear 2 Close the flushing valve tight For periodic inspection and cleaning of screens f...

Page 5: ... 1215 47 8 B 184 7 2 228 9 0 334 13 1 388 15 3 416 16 4 502 19 8 515 20 3 554 21 8 W 215 8 5 280 11 0 355 14 0 440 17 3 540 21 3 620 24 4 665 26 2 720 28 3 C 20 0 75 25 1 25 1 40 1 5 40 1 5 50 2 40 2 50 2 D 3 2 0 13 3 2 0 13 3 2 0 13 3 2 0 13 3 2 0 13 3 2 0 13 3 2 0 13 3 2 0 13 Flushing Valve Length 226 8 9 226 8 9 203 8 203 8 203 8 203 8 229 9 254 10 F 2 ISO 7 Rp 2 ISO 7 Rp 3 150 3 150 3 150 3 15...

Page 6: ...low coefficient Kv flow in m h at 1 bar differential pressure Cv flow in gpm at 1 psi differential pressure The pressure loss calculation formula Δp SG Q Cv or Kv 2 2 Leq Equivalent pipe length for turbulent flow in clean commercial steel pipe SCH 40 3 Max allowable pressure drop 7 psi 0 5 bar across the strainer basket screen shall be cleaned when pressure drop exceeds this value at maximum flow ...