FP-60F-D/DV

Installation 

Provide basket removal clearances and strainer installation provisions in accordance with the requirements given in 
the Design Engineer Guide section above. Install the strainer with the flow arrow on the body pointing in the desired 
flow direction. 
The strainer should be installed such that the flushing valve Drain Flange is at the lowest point of the strainer, 3" to 
12" strainers have the flushing valve port on the cover that can be rotated to be at the lowest point, this is to facilitate 
efficient cleaning of the screen while flushing.
The strainer shall be installed on the pipeline upstream of the sprinklers, pressure control valve, deluge valve or any 
other sensitive system device. Install a listed isolating valve upstream of the strainer. An adequate support shall be 
provided to carry the system installation as well as the dynamic loads.
It is recommended to install a differential pressure gauge rooted to upstream and downstream of the FP-60F-D/DV 
strainer, in order to show the degree of strainer blockage. The maximum allowable differential pressure across the 
strainer is 7 psi or 0.5 bar at maximum system flow.

Placing In Service 

Verify that all strainer cover bolts are well tightened, close the drain plug and/or drain valve, slowly open the supply-
isolating valve and check that there are no leakages. Observe the system pressure gauge: it should indicate that the 
normal supply of water pressure is maintained.

Typical Installations

The BERMAD FP-60F-D/DV strainer is ideal to be installed 
upstream of the BERMAD Pressure Control Valve, preventing 
the fouling of valve sealing surfaces and keeping the 
waterways clear from obstructions.

The BERMAD FP-60F-D/DV strainer should be installed 
upstream of the Deluge, Foam system or Automatic Sprinkler 
system, preventing debris particles from clogging the 
nozzles and other sensitve devices.

Automatic Pressure Control System 

Deluge / Sprinkler System

Summary of Contents for FP-60F-D

Page 1: ...sted strainers shall be provided in the main pipeline of all systems using nozzles where the water is likely to contain obstructive material Features and Benefits UL Listed and ULC size for Fire systems Low pressure drop Safety and reliability ensures firewater availability Easy in line maintenance Large diameter flushing valve for fast and easy interim cleaning Suitable to prevent clogging Nozzle...

Page 2: ... area ratio of 10 1 shall be used with foam proportioners or foam generators and should be installed in the water pipeline upstream of the water control valve The NFPA 13 15 and 16 standards stipulate that a Listed Strainer shall be provided in the main pipeline of all systems utilizing nozzles with waterways less than 3 8 9 5 mm and for any system where the water is likely to contain obstructive ...

Page 3: ...ll as the dynamic loads It is recommended to install a differential pressure gauge rooted to upstream and downstream of the FP 60F D DV strainer in order to show the degree of strainer blockage The maximum allowable differential pressure across the strainer is 7 psi or 0 5 bar at maximum system flow Placing In Service Verify that all strainer cover bolts are well tightened close the drain plug and...

Page 4: ...isassembly of any strainer component The strainer basket screen should be cleaned after each system operation or flow test and during routine inspections as follows For strainers fitted with a flushing valve 1 Fully open the flushing drain valve for at least 5 seconds or until the flushed water becomes visibly clear 2 Close the flushing valve tight For periodic inspection and cleaning of screens f...

Page 5: ... 1215 47 8 B 184 7 2 228 9 0 334 13 1 388 15 3 416 16 4 502 19 8 515 20 3 554 21 8 W 215 8 5 280 11 0 355 14 0 440 17 3 540 21 3 620 24 4 665 26 2 720 28 3 C 20 0 75 25 1 25 1 40 1 5 40 1 5 50 2 40 2 50 2 D 3 2 0 13 3 2 0 13 3 2 0 13 3 2 0 13 3 2 0 13 3 2 0 13 3 2 0 13 3 2 0 13 Flushing Valve Length 226 8 9 226 8 9 203 8 203 8 203 8 203 8 229 9 254 10 F 2 ISO 7 Rp 2 ISO 7 Rp 3 150 3 150 3 150 3 15...

Page 6: ...low coefficient Kv flow in m h at 1 bar differential pressure Cv flow in gpm at 1 psi differential pressure The pressure loss calculation formula Δp SG Q Cv or Kv 2 2 Leq Equivalent pipe length for turbulent flow in clean commercial steel pipe SCH 40 3 Max allowable pressure drop 7 psi 0 5 bar across the strainer basket screen shall be cleaned when pressure drop exceeds this value at maximum flow ...

Reviews: