6-12
Close and Reclose Logic
Date Code 20011205
SEL-311B Instruction Manual
Note:
A transient synchronism check condition across open circuit breaker 52/2 could possibly
occur if circuit breaker 52/1 recloses into a fault on one phase of the transmission line.
The other two unfaulted phases would be briefly energized until circuit breaker 52/1 is
tripped again. If channel VS of the SEL-311B(2) Relay is connected to one of these
briefly energized phases, synchronism check element 25A1 could momentarily assert to
logical 1.
So that this possible momentary assertion of synchronism check element 25A1 does not
cause any inadvertent reclose of circuit breaker 52/2, make sure the open interval timers
in the SEL-311B(2) Relay are set with some appreciable time greater than the momentary
energization time of the faulted transmission line. Or, run the synchronism check element
25A1 through a programmable timer before using it in the preceding 79CLS and 79STL
settings for the SEL-311B(2) Relay (see Figure 7.23 and Figure 7.24). Note the built-in
3-cycle qualification of the synchronism check voltages shown in Figure 3.24.
Additional Settings Example 2
Refer to subsection
Synchronism Check Elements
in
Section 3: Distance, Overcurrent,
Voltage, and Synchronism Check Elements
. Also refer to Figure 6.3 and Figure 6.4.
If the synchronizing voltages across open circuit breaker 52/2 are “slipping” with respect to one
another, the Reclose Supervision Limit Timer setting 79CLSD should be set greater than zero so
there is time for the slipping voltages to come into synchronism. For example:
79CLSD = 60.00 cycles
79CLS =
25A1
The status of synchronism check element 25A1 is checked continuously during the 60-cycle
window. If the slipping voltages come into synchronism while timer 79CLSD is timing,
synchronism check element 25A1 asserts to logical 1 and reclosing proceeds.
In the above referenced subsection
Synchronism Check Elements
, note item 3 under
Synchronism Check Element Outputs
, Voltages V
P
and V
S
are “Slipping.” Item 3 describes a
last attempt for a synchronism check reclose before timer 79CLSD times out (or setting 79CLSD
= 0.00 and only one check is made).
R
ECLOSING
R
ELAY
Note that input:
Reclosing Relay Open Interval Time-Out
in Figure 6.2 is the logic input that is qualified by SEL
OGIC
control equation setting 79CLS, and
then propagated onto the close logic in Figure 6.1 to automatically reclose a circuit breaker. The
explanation that follows in this reclosing relay subsection describes all the reclosing relay
settings and logic that eventually result in this open interval time-out logic input into Figure 6.2.
Other aspects of the reclosing relay are also explained. Up to four (4) automatic reclosures
(shots) are available.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......