Date Code 20011205
Configuration, Fast Meter, and Fast Operate Commands
D-11
SEL-311B Instruction Manual
ID Message
In response to the ID command, the relay sends the following information described below.
<STX>"FID=SEL-311B-Rrrr-Vv-Zzzzzzz-Dyyyymmdd","aaaa"<CR><LF>
"CID=cccc","aaaa"<CR><LF>
"DEVID=[TID SETTING]","aaaa"<CR><LF>
"DEVCODE=47","aaaa"<CR><LF>
"PARTNO=[PARTNO SETTING]","aaaa"<CR><LF>
"CONFIG=bbbbbb","aaaa"<CR><LF><ETX>
Where: rrr is the firmware revision.
zzzzzz
is
settings and protocol version numbers.
cccc is the 4-digit firmware checksum.
yyyy is the 4-digit year code.
mm is the 2 digit month code.
dd is the 2-digit day code.
bbbbbb is the 6-digit configuration code.
aaaa is an ASCII representation of the 2-byte checksum for each line.
FID is the Firmware identification string.
CID is the 4 digit hexadecimal checksum of the firmware.
DEVID is the text from the Relay Identification (RID) setting.
DEVCODE is the MODBUS Device ID Code for the SEL-311B.
PARTNO is the part number that matches the Model Option Table number.
CONFIG is configuration string used for SEL internal use only.
The ID message is available from Access Level 1 and higher.
DNA Message
In response to the DNA command, the relay sends names of the Relay Word bits transmitted in
the A5D1 message. The first name is associated with the MSB, the last name with the LSB.
These names are listed in the Relay Word Bits table for the appropriate model in
Section 9: Setting the Relay
of this manual. The DNA command is available from Access
Level 1 and higher.
The DNA message is:
<STX>
"EN","TRP","TIME","TARDT","SOTF","RCRS","RCCY","RCLO","0C8E"
"A","B","C","G","ZONE1","ZONE2","ZONE3","51","093D"
"M1P","M1PT","Z1G","Z1GT","M2P","M2PT","Z2G","Z2GT","0B54"
"Z1T","Z2T","50P1","67P1","67P1T","50G1","67G1","67G1T","0B50"
"51G","51GT","51GR","LOP","ILOP","ZLOAD","ZLOUT","ZLIN","0CA1"
"LB1","LB2","LB3","LB4","LB5","LB6","LB7","LB8","0994"
"LB9","LB10","LB11","LB12","LB13","LB14","LB15","LB16","0AE5"
"RB1","RB2","RB3","RB4","RB5","RB6","RB7","RB8","09C4"
"RB9","RB10","RB11","RB12","RB13","RB14","RB15","RB16","0B15"
"LT1","LT2","LT3","LT4","LT5","LT6","LT7","LT8","0A24"
"LT9","LT10","LT11","LT12","LT13","LT14","LT15","LT16","0B75"
"SV1","SV2","SV3","SV4","SV1T","SV2T","SV3T","SV4T","0BAC"
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......