14-38
Application Settings for SEL-221 Series Relays
Date Code 20011205
SEL-311B Instruction Manual
SEL-311B
Relay
Setting
Calculated from SEL-221C
Settings
SEL-311B Instruction
Manual Section
SEL-221C Instruction
Manual Section
79OI1
= 79OI1
Section 6—Close and
Reclose Logic
Section 2—Reclosing
Relay
79OI2 =
79OI2
79OI3 =
79OI3
79RSD
None (SEL-221C setting 79RS
serves a slightly different
purpose.)
Section 6—Reclosing
Relay Timer Settings
79RSLD None
52AEND
= 52BT (Pickup)
Section 5—Switch-
Onto-Fault (SOTF) Trip
Logic
Section 5—52BT
Setting (52BT) and
Switch-Onto-Fault
Protection
SOTFD
= 52BT (Dropout)
TDURD
= TDUR
Section 4—Unlatch
Trip
Section 5—Trip
Duration Timer
(TDUR)
SV1PU
= 50MFD
Section 5—Medium Set
Overcurrent Setting
(50M)
SV9DO
= VCT
Section 2—Reclosing
Relay
* Curve U1 in the SEL-311B is slightly different from curve 1 in the SEL-221C. Time dial
adjustments may be necessary.
Note:
SEL-311B phase-to-phase fault detector settings 50PP1, 50PP2, and 50PP3 are set to
0.1 * I
NOM
and are hidden. This corresponds to SEL-221C setting 50L.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......