7-38
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20011205
SEL-311B Instruction Manual
Make corresponding, complementary text settings:
DP1_1 = 79 ENABLED
DP1_0 = 79 DISABLED
Display point setting DP1 controls the display of the text settings.
Reclosing Relay Enabled
In Figure
7.28, optoisolated input IN102 is energized to enable the reclosing relay, resulting in:
DP1
= IN102 = logical 1
This results in the display of corresponding text setting DP1_1 on the front-panel display:
79 ENABLED
Reclosing Relay Disabled
In Figure
7.28, optoisolated input IN102 is deenergized to disable the reclosing relay, resulting
in:
DP1
= IN102 = logical 0
This results in the display of corresponding text setting DP1_0 on the front-panel display:
79 DISABLED
Circuit Breaker Status Indication
Make SEL
OGIC
control equation display point setting DP2:
DP2 =
IN101
Make corresponding, complementary text settings:
DP2_1 = BREAKER CLOSED
DP2_0 = BREAKER OPEN
Display point setting DP2 controls the display of the text settings.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......