13-22
Testing and Troubleshooting
Date Code 20011205
SEL-311B Instruction Manual
Relay word bit 32QE asserts when both the 3I
2
magnitude condition and the magnitude
comparison of positive-sequence current to negative-sequence current are satisfied. This relay
word bit supervises the F32Q and R32Q elements. The F32QG and R32QG elements require
further supervision.
Magnitude Comparison of Zero-Sequence Current to Negative-Sequence Current
The relay multiplies the measured zero-sequence current (I
1
) magnitude by the k2 setting, then
compares the result to the measured magnitude of negative-sequence current (I
2
). The magnitude
of I
2
must be greater than the magnitude of I
0
multiplied by k2 for the directional elements
F32QG or R32QG to operate.
Loss-of-Potential Supervision
If ELOP = Y or Y1 the relay supervises the directional logic using the Internal Loss-of-Potential
condition (ILOP). If ELOP = Y the relay sets the 32QF element and disables F32Q, F32QG,
R32Q, and R32QG when a loss-of-potential is detected, regardless of other signals applied to the
relay. If you test the directional logic using single voltage and current sources, set ELOP = N to
simplify the test.
Negative-Sequence Directional Element Test Using Single Voltage and Current Sources
Step 1.
Execute the
SHOWSET
command and verify the following relay settings: Z1MAG,
Z1ANG, Z2F, 50QF, Z2R, 50QR, and a2. The example relay settings use the
following settings: Z1MAG = 7.8
W
, Z1ANG = 83.97°, Z2F = 0.77
W
; 50QF = 0.5
amps secondary; Z2R = 5.45
W
; 50QR = 0.5 amps secondary; a2 = 0.07, k2 = 0.2
Execute the
SET
command and change the example ELOP setting from Y to N.
Step 2.
Select output contacts to indicate operation of the F32Q and R32Q elements. In this
example we use the OUT106 and OUT107 outputs.
From Access Level 2, execute the
SET L n
command to configure Output 6 and
Output 7 to close for assertion of the F32Q and R32Q elements, respectively.
=>>SET L 1 OUT106 <ENTER>
SET L 1 OUT106 <ENTER>
SET L 1 OUT106 <ENTER>
SET L 1 OUT106 <ENTER>
SELogic group 1
OUT106 =0
? F32Q <ENTER>
F32Q <ENTER>
F32Q <ENTER>
F32Q <ENTER>
OUT107 =0
? R32Q <ENTER>
R32Q <ENTER>
R32Q <ENTER>
R32Q <ENTER>
DP1 =52A
? END <ENTER>
END <ENTER>
END <ENTER>
END <ENTER>
After you type
END <ENTER>
to end the set procedure, the relay displays the
current logic settings. At the prompt, type
Y <ENTER>
to accept those settings.
Connect outputs OUT106 and OUT107 to the sense input of your test set, an
ohmmeter, or some other contact sensing device.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......