Date Code 20011205
Inputs, Outputs, Timers, and Other Control Logic
7-39
SEL-311B Instruction Manual
Circuit Breaker Closed
In Figure
7.28, optoisolated input IN101 is energized when the 52a circuit breaker auxiliary
contact is closed, resulting in:
DP2
= IN101 = logical 1
This results in the display of corresponding text setting DP2_1 on the front-panel display:
BREAKER CLOSED
Circuit Breaker Open
In Figure
7.28, optoisolated input IN101 is deenergized when the 52a circuit breaker auxiliary
contact is open, resulting in:
DP2
= IN101 = logical 0
This results in the display of corresponding text setting DP2_0 on the front-panel display:
BREAKER OPEN
Additional Settings Examples
Display Only One Message
To display just one screen, but not its complement, set only one of the text settings. For
example, to display just the “breaker closed” condition, but not the “breaker open” condition,
make the following settings:
DP2
= IN101
(52a circuit breaker auxiliary contact connected to input
IN101—see Figure
7.28)
DP2_1 = BREAKER CLOSED
(displays when DP2 = logical 1)
DP2_0 =
(blank)
Circuit Breaker Closed
In Figure
7.28, optoisolated input IN101 is energized when the 52a circuit breaker auxiliary
contact is closed, resulting in:
DP2
= IN101 = logical 1
This results in the display of corresponding text setting DP2_1 on the front-panel display:
BREAKER CLOSED
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......