Date Code 20011205
Close and Reclose Logic
6-1
SEL-311B Instruction Manual
SECTION 6: CLOSE AND RECLOSE LOGIC
O
VERVIEW
This section is made up of three subsections:
Close Logic
This subsection describes the final logic that controls the close output contact (e.g.,
OUT103 = CLOSE). This output contact closes the circuit breaker for automatic
reclosures and other close conditions (e.g., manual close initiation via serial port or
optoisolated inputs).
If automatic reclosing is not needed, but the SEL-311B Relay is to close the circuit
breaker for other close conditions (e.g., manual close initiation via serial port or
optoisolated inputs), then this subsection is the only subsection that needs to be read in
this section (particularly the description of SEL
OGIC
®
control equation setting CL).
Reclose Supervision Logic
This subsection describes the logic that supervises automatic reclosing when an open
interval time times out—a final condition check right before the close logic asserts the
close output contact.
Reclose Logic
This subsection describes all the reclosing relay settings and logic needed for automatic
reclosing (besides the final close logic and reclose supervision logic described in the
previous subsections).
The reclose enable setting, E79, has setting choices N, 1, 2, 3, and 4. Setting E79 = N
defeats the reclosing relay. Setting choices 1 through 4 are the number of desired
automatic reclosures.
Note:
Setting E79 = N defeats the reclosing relay, but does not defeat the ability of the close
logic described in the first subsection (Figure 6.1) to close the circuit breaker for other
close conditions via SEL
OGIC
control equation setting CL (e.g., manual close initiation
via serial port or optoisolated inputs).
C
LOSE
L
OGIC
The close logic in Figure 6.1 provides flexible circuit breaker closing/automatic reclosing with
SEL
OGIC
control equation settings:
52A (breaker
status)
CL
(close conditions, other than automatic reclosing)
ULCL
(unlatch close conditions, other than circuit breaker status, close failure, or
reclose initiation)
and setting:
CFD
(Close Failure Time)
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......