Close and Reclose Logic
6-13
SEL-311B Instruction Manual
The reclose enable setting, E79, has setting choices N, 1, 2, 3, and 4. Setting E79 = N defeats the
reclosing relay. Setting choices 1 through 4 are the number of desired automatic reclosures (see
Open Interval Timers
that follows in this subsection).
Reclosing Relay States and General Operation
Figure 6.5 explains in general the different states of the reclosing relay and its operation.
Figure 6.5: Reclosing Relay States and General Operation
Table 6.1: Relay Word Bit and Front-Panel Correspondence to Reclosing Relay States
Reclosing Relay State
Corresponding
Relay Word Bit
Corresponding
Front-Panel LED
Reset 79RS RS
Cycle 79RCY CY
Lockout 79LO LO
The reclosing relay is in one (and only one) of these states (listed in Table 6.1) at any time.
When in reset or lockout, the corresponding Relay Word bit asserts to logical 1, and the LED
illuminates. Automatic reclosing only takes place when the relay is in the Reclose Cycle State.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......