Date Code 20011205
Introduction and Specifications
1-13
SEL-311B Instruction Manual
Under---- and Overvoltage Elements
Pickup Range:
OFF, 0.00–150.00 V, 0.01 V steps (phase elements)
OFF, 0.00–260.00 V, 0.01 V steps (phase-to-phase elements)
Steady-State Pickup Accuracy:
±1 V and ±5% of setting
Transient Overreach:
< 5% of pickup
Synchronism-Check Elements
Slip Frequency Pickup Range:
0.005–0.500 Hz, 0.001 Hz steps
Slip Frequency Pickup Accuracy:
±0.003 Hz
Phase Angle Range:
0–80°, 1° steps
Phase Angle Accuracy:
±
4°