SECTION 06B: ELECTRICAL
22
DOB 2490-2789 | X3-45 Commuter PA1605 Maintenance Manual (Final Version – Rev.2 April 2016)
FMI 4
Shorted Low
Output A45 J1:20
shorted to ground
Electrical horn
L185 and L186
not working
•
A45 module failure
•
Electrical horn L185 or L186
failure
•
Connector C4 corroded
•
Connector C101 corroded
•
Circuit 52A shorted to ground
FMI 5
Open Circuit
A45 module does not
detect Electrical horn
L185 or L186
Electrical horn
L185 and L186
not working
•
A45 module failure
•
Electrical horn L185 or L186
open circuit
•
Circuit 52A open
FMI 6
Current
above normal
Output A45 J1:20
internal software fuse
active for overcurrent
Electrical horn
L185 and L186
not working
•
A45 module failure
•
Connector C4 corroded
•
Connector C101 corroded
•
Circuit 52A shorted to ground
MID 188 PSID # 110 Indir Lts Rly (A49 J1:12)
Type of
fault:
FMI
Description:
Fault Condition:
Possible
Symptoms:
Possible Causes:
FMI 3
Shorted High
Voltage present on
output A49 J1:12 but
output not active
Indirect lighting
always ON
•
A49 module failure
•
Indirect Light Relay R13 failure
•
Circuit 132 shorted to battery
FMI 4
Shorted Low
Output A49 J1:12
shorted to ground
Indirect lighting
not working
•
A49 module failure
•
Indirect Light Relay R13 failure
•
Circuit 132 shorted to ground
FMI 5
Open Circuit
A49 module does not
detect Indirect Light
Relay R13
Indirect lighting
not working
•
A49 module failure
•
Indirect Light Relay R13 open
circuit
•
Circuit 132 open
FMI 6
Current
above normal
Output A49 J1:12
internal software fuse
active for overcurrent
Indirect lighting
not working
•
A49 module failure
•
Circuit 132 shorted to ground
•
Relay R13 coil shorted to
ground
MID 188 PSID # 89 Knee down Sol (A41 J1:14)
Type of
fault:
FMI
Description:
Fault Condition:
Possible
Symptoms:
Possible Causes:
FMI 3
Shorted High
Voltage present on
output A41 J1:14 but
output not active
Kneeling down
always ON,
coach cannot
be raised
•
A41 module failure
•
Kneeling down solenoid valve
So16 failure
•
Connector C4 corroded
•
Connector C172 corroded
•
Circuit 126F shorted to battery
FMI 4
Shorted Low
Output A41 J1:14
shorted to ground
Kneeling down
not working
•
A41 module failure
•
Kneeling down solenoid valve
So16 failure
•
Connector C4 corroded
•
Connector C172 corroded