4-38
Pr4.28
Title
Analog input 3 (AI3) offset setup
Related
control mode
P S T F
Range
−342 to 342
Unit
5.86mV
Default
0
Set up the offset correction value applied to the voltage fed to the analog input 3.
Pr4.29
Title
Analog input 3 (AI3) filter
Related
control mode
P S T F
Range
0 to 6400
Unit
0.01ms
Default
0
Set up the time constant of 1st delay filter that determines the lag time behind the voltage
applied to the analog input 3.
Pr4.30
Title
Analog input 3 (AI3) overvoltage setup
Related
control mode
P S T F
Range
0 to 100
Unit
0.1V
Default
0
Set up the excessive level of the input voltage of analog input 3 by using the voltage
associated with offset.
Pr4.31
Title
Positioning complete (In-position) range
Related
control mode
P
S T
F
Range
0 to 262144
Unit
Command
unit
Default
10
Caution
Set up the timing of positional deviation at which the positioning complete signal (INP1) is output.
The command unit is used as the default unit but can be replaced by the encoder unit by
using Pr5.20. Positioning unit selection. Note that when the encoder unit is used, unit of
Pr0.14 Positional deviation excess setup is also changed.
Pr4.32
Title
Positioning complete (In-position) output setup
Related
control mode
P
S T
F
Range
0 to 3
Unit
—
Default
0
Select the condition to output the positioning complete signal (INP1).
Setup value
Action of positioning complete signal
0
The signal will turn on when the positional deviation is smaller than Pr4.31 (Positioning
complete range)
1
The signal will turn on when there is no position command and the positional
deviation is smaller than Pr4.31 (Positioning complete range).
2
The signal will turn on when there is no position command, the zero-speed detection signal
is ON and the positional deviation is smaller than Pr4.31 (Positioning complete range).
3
The signal will turn on when there is no position command and the positional devia
tion
is smaller than Pr4.31 (Positioning complete range). Then holds "ON" status until the
next position command is entered.Subsequently, ON state is maintained until Pr4.33
INP hold time has elapsed. After the hold time, INP output will be turned ON/OFF ac-
cording to the coming positional command or condition of the positional deviation.
1. Details of parameter
[Class 4] I/F monitor setting