4-19
1
Before
Using
the
Products
2
Preparation
3
Connection
4
Setup
5
Adjustment
6
When
in
Trouble
7
Supplement
Pr2.00
Title
Adaptive filter mode setup
Related
control mode
P S
T
F
Range
0 to 4
Unit
—
Default
0
Set up the resonance frequency to be estimated by the adaptive filter and specify the
operation after estimation.
Setup value
Content
0
Adaptive filter:
invalid
Parameters related to the 3rd and 4th notch filter hold the
current value.
1
Adaptive filter:
1 filter is valid
One adaptive filter is enabled. Parameters related to the 3rd
notch filter will be updated based on adaptive performance.
2
Adaptive filter:
2 filters are valid
Two adaptive filters are enabled. Parameters related to the
3rd and 4th notch filters will be updated based on adaptive
performance.
3
Resonance frequency
measurement mode
Measure the resonance frequency. Result of measurement
can be checked with PANATERM. Parameters related to the
3rd and 4th notch filter hold the current value.
4
Clear result of
adaptation
Parameters related to the 3rd and 4th notch filter are
disabled and results of adaptive operation are cleared.
Pr2.01
Title
1st notch frequency
Related
control mode
P S T F
Range
50 to 5000
Unit
Hz
Default
5000
Caution
Set the center frequency of the 1st notch filter.
The notch filter function will be invalidated by setting up this parameter to "5000".
Pr2.02
Title
1st notch width selection
Related
control mode
P S T F
Range
0 to 20
Unit
—
Default
2
Caution
Set the width of notch at the center frequency of the 1st notch filter.
Higher the setup, larger the notch width you can obtain. Use with default setup in normal
operation.
Pr2.03
Title
1st notch depth selection
Related
control mode
P S T F
Range
0 to 99
Unit
—
Default
0
Caution
Set the depth of notch at the center frequency of the 1st notch filter.
Higher the setup, shallower the notch depth and smaller the phase delay you can obtain.
Pr2.04
Title
2nd notch frequency
Related
control mode
P S T F
Range
50 to 5000
Unit
Hz
Default
5000
Caution
Set the center frequency of the 2nd notch filter.
The notch filter function will be invalidated by setting up this parameter to "5000".
4
1. Details of parameter
Setup
[Class 2] Damping control
Summary of Contents for MINAS A5-series