background image

1

63-2202—3

CONTENTS

Specifications ................................................. 2
Ordering Information ..................................... 2
Installation ..................................................... 4
Settings and Adjustments .............................. 10
Operation and Checkout .............................. 11

 G. R.  •  Rev. 8-93  •  ©Honeywell Inc. 1993  •  Form Number 63-2202—3

The M72XX series Modutrol IV Motors are

used to control dampers and valves. The mo-
tors accept a current or voltage signal from an
electronic controller to position a damper or
valve at any point between open and closed.

Replaces M744S,T,Y and M745S,T,Y Motors.

M7261, M7274, M7281, M7284, and M7294 are
non-spring return motors; M7272, M7282, M7285,
and M7286 are spring return motors.

Oil immersed motor and gear train for reliable per-
formance and long life.

Wiring box provides NEMA 3 weather protection.

Actuator motor and circuitry operate from 24 Vac.
Models available with factory installed transformer
or an internal transformer can be field added.

Quick connect terminals standard—screw termi-
nal adapter available.

Adapter bracket for matching shaft height of older
motors is standard with replacement motors.

Nominal timing of 30 seconds for 90

°

 stroke and

60 seconds for 160

°

 stroke.

Valve and damper linkages, explosion proof hous-
ing, and auxiliary switches available as accessories.

Spring return motors are rated for 25 lb.-in. and
60 lb.-in torque.

Non-spring return motors are rated for 35 lb.-in.,
75 lb.-in., 150 lb.-in., and 300 lb.-in. torque.

Models available with adjustable start (zero) and
span.

Models available with 4 to 20 mA input signal.

Models available with 2 to 10 Vdc input signal.

Die-cast magnesium housing.

M7261, M7272, M7274, M7281,
M7282, M7284, M7285, M7286,

M7294 Modutrol IV Motors

Summary of Contents for Modutrol IV M72 Series

Page 1: ... Actuator motor and circuitry operate from 24 Vac Models available with factory installed transformer or an internal transformer can be field added Quick connect terminals standard screw termi nal adapter available Adapter bracket for matching shaft height of older motors is standard with replacement motors Nominal timing of 30 seconds for 90 stroke and 60 seconds for 160 stroke Valve and damper l...

Page 2: ...wiserotationasviewed from the power end of the motor Open The limit of clockwise rotation as viewed from the power end of the motor MechanicallyNormallyClosed Springreturn normally closed motors rotate to the closed position on loss of power Mechanically Normally Open Spring return normally open motors rotate to the open position on loss of power Electrically Normally Closed Both spring return and...

Page 3: ...P VIEW OF BRACKET ONLY 3 93 100 4 22 107 2 3 58 64 16 67 17 4 88 124 43 11 5 54 141 27 7 5 82 148 2 POWER END 4 5 37 136 1 FOR HIGH TORQUE 60 LB IN SPRING RETURN MODELS 3 9 98 FOR LOW TORQUE 25 LB IN SPRING RETURN MODELS 3 4 85 5 FOR NON SPRING RETURN MODELS 2 4 61 2 FOR HIGH TORQUE 60 LB IN SPRING RETURN MODELS 8 76 222 5 FOR LOW TORQUE 25 LB IN SPRING RETURN MODELS 8 26 209 8 NON SPRING RETURN M...

Page 4: ...e use of an adapter bracket Ap proximately0 75in 19mm shorterthanthe7616BR Crank Arm 220741A Screw Terminal Adapter converts the stan dard quick connect terminals to screw terminals Transformers Mountedinternally provide24Vacpower to the motor 198162JA 24 Vac 50 60 Hz for electrical isolation 198162EA 120 Vac 50 60 Hz 198162GA 220 Vac 50 60 Hz 198162AA 120 208 240 Vac 50 60 Hz 4074ERU Weatherproof...

Page 5: ...he bolts through the outer set of back slots of the motor flange and into the outer threaded holes of the bracket LINKAGES Use of the 220738A Adapter Bracket packed with the motor is optional for many damper applications Use the bracket in damper applications requiring the crank arm to rotate through the bottom plane of the motor If you do not use the bracket you will have to adjust the damper lin...

Page 6: ...unting the motor with an adapter bracket M452D EQUIPMENT BASE ADAPTER BRACKET STANDARD BOLTS 4 MOTOR BOLTS PROVIDED 4 WIRING BOX POWER END POWER END NON SPRING RETURN SPRING RETURN 1 12 OR 1 4 ZINC PLATED MACHINE SCREWS OR BOLTS 1 P O W E R E N D P O W E R E N D P O W E R E N D ...

Page 7: ...LVE STANDARD BOLTS M5776 MOTOR WIRING BOX BOLTS PROVIDED 4 POWER END OF MOTOR MOTOR BOLTS PROVIDED 4 WIRING BOX POWER END OF MOTOR NON SPRING RETURN SPRING RETURN 1 2 1 12 OR 1 4 ZINC PLATED MACHINE SCREWS OR BOLTS 2 FASTEN ADAPTER BRACKET TO VALVE LINKAGE AND HAND TIGHTEN BOLTS SECURE MOTOR TO BRACKET USING FOUR BOLTS PROVIDED THEN TIGHTEN BRACKET TO LINKAGE BOLTS ...

Page 8: ...ring compartment is gained by removing the four screws on the top of the wiring box and lifting off the cover See Fig 5 for terminal locations See Fig 6 for the internal schematic Fig 7 shows connections for typical system applications Fig 8 shows parallel motor connections Fig 5 Terminals and adjustments RIGHT INNER AUXILIARY SWITCH INNER AUXILIARY SWITCH CAM BLUE POWER END OUTER AUXILIARY SWITCH...

Page 9: ...TOR MOTOR MOTOR 2 F T1 T2 2 F T1 T2 2 F T1 T2 2 When used with liquid tight conduit connectors the wiring box provides NEMA 3 weather resistance for the motor The wiring box standard with replacement motors also provides knockouts for wiring conduits and encloses terminals The wiring box is required for housing an inter nal transformer or internal auxiliary switches Wire the motor as follows 1 Rem...

Page 10: ...UST ZERO ADJUST AND SPAN ADJUST POTENTIOMETERS TO ACHIEVE DESIRED SEQUENCE 2 3 SEQUENTIAL OPERATION OF THREE M91XX MOTORS USING Q7230 M2893 AUXILIARY SWITCH SETTING PROCEDURE See Fig 10 CAUTION 1 Live circuits are exposed during the auxiliary switch adjustment procedure Always turn off the power before adjusting switch cams 2 Do not turn motor shaft by hand or with a wrenchbecausedamagetothemotorc...

Page 11: ... from the controller changes and unbalance is amplified to energize the Triac switching to run the motor in the proper direction to correct the change in the temperature or the pressure The motor turns the feedback potentiometer to rebalance the circuit and stop the motor CHECKOUT After installation and linkage adjustment operate the motor through the controller Make sure that The motor properly o...

Page 12: ...ome and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Reviews: