Appendices
A-92
CP2E CPU Unit Software User’s Manual(W614)
A583
00
I/O Memory Backup
Error Flag
The flag will be ON when the I/O
memory is not held at power ON.
It will still be ON until the memory area
is cleared or the flag is turned OFF
manually.
ON: I/O memory
backup error
occurred
OFF: Normal
Retained
Retained
Refreshed
when the
power is
turned ON.
A403.14
A616
00
Serial Port 1 (EX)
Communication
Settings
Display the present communication
settings of the serial port 1 (EX).
Reflect the PLC Setup when power is
turned ON.
Parity
0: Even
1: Odd
Retained
See
Function
column.
Refreshed
when power is
turned ON.
01
Parity
0: Yes
1: No
Retained
See
Function
column.
Refreshed
when power is
turned ON.
02
Stop bit
0: 2 bits
1: 1 bit
Retained
See
Function
column.
Refreshed
when power is
turned ON.
03
Data length
0: 7 bits
1: 8 bits
Retained
See
Function
column.
Refreshed
when power is
turned ON.
04
Start bit
0: 1 bit (fixed)
Retained
See
Function
column.
Refreshed
when power is
turned ON.
08
to
11
Communication
speed
0 hex: Default (9600)
3 hex: 1200
4 hex: 2400
5 hex: 4800
6 hex: 9600
7 hex: 19200
8 hex: 38400
9 hex: 57600
A hex: 115200
Retained
See
Function
column.
Refreshed
when power is
turned ON.
12
to
15
Communication
mode
0 hex: Default (Host
Link)
3 hex: Non-protocol
5 hex: Host Link
7 hex: Serial PLC
Link (Slave)
8 hex: Serial PLC
Link (Master)
9 hex: Modbus-RTU
Easy Master
Retained
See
Function
column.
Refreshed
when power is
turned ON.
Address
Name
Function
Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
flags,
settings
Words
Bits
Summary of Contents for SYSMAC CP Series
Page 3: ......
Page 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Page 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Page 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Page 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Page 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Page 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Page 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Page 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Page 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Page 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Page 577: ......