5-15
5 I/O Memory
CP2E CPU Unit Software User’s Manual(W614)
5-7
Cou
n
te
r A
rea (C)
5
5-7
Counter Area (C)
The Counter Area contains Completion Flags (1 bit each) and counter PVs (16 bits each). A Comple-
tion Flag is turned ON when the counter PV reaches the set value (counting out).
Completion Flags and counter PVs are automatically retained in the built-in non-volatile RAM even if
the power supply is interrupted.
Counter numbers range from C0 to C255.
.
z
Types of Counters
The following table shows which instructions are used to refresh counter PVs in BCD and binary
mode.
Counter numbers 0 to 255 are used by all counters given above.
Built-in high-speed counters 0 to 5 do not use counter numbers.
Overview
Notation
Range
Details
Counter instruction
BCD mode
Binary mode
COUNTER
CNT
CNTX
REVERSIBLE COUNTER
CNTR
CNTRX
C 002
Co
u
nter n
u
m
b
er: 002
I/O memory area designator: C
Summary of Contents for SYSMAC CP Series
Page 3: ......
Page 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Page 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Page 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Page 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Page 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Page 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Page 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Page 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Page 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Page 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Page 577: ......