8
Overview of Built-in Functions and Allocations
8-2
CP2E CPU Unit Software User’s Manual(W614)
8-1
Built-in Functions
The following built-in functions are provided by the CP2E CPU Units.
Type
Function
CP2E E
-type CPU Units
CP2E S
-type CPU Units
CP2E N
-type CPU Units
Reference
Appearance
Quick-response inputs
6 inputs
6 inputs
N14 CPU Units: 6 inputs
N20/
3
0/40/60 CPU Units:
8
inputs
Section 9
Input interrupts
6 inputs
6 inputs
N14 CPU Units: 6 inputs
N20/
3
0/40/60 CPU Units:
8
inputs
Section 10
Scheduled interrupts
1 interrupt
1 interrupt
1 interrupt
High-speed counter
•
Incremental: 100 kHz
×
2
counters, 10 kHz
×
4 counters
•
Up/down: 100 kHz
×
1
counter, 10 kHz
×
1 counter
•
Pulse plus direction: 100
kHz
×
2 counters
•
Differential phases (4
×
): 50
kHz
×
1 counter, 5 kHz
×
1
counter
•
Incremental: 100 kHz
×
2
counters, 10 kHz
×
4 counters
•
Up/down: 100 kHz
×
1
counter, 10 kHz
×
1 counter
•
Pulse plus direction: 100
kHz
×
2 counters
•
Differential phases (4
×
): 50
kHz
×
1 counter, 5 kHz
×
1
counter
N14/20 CPU Units:
•
Incremental: 100 kHz
×
2
counters, 10 kHz
×
4 counters
•
Up/down: 100 kHz
×
1 counter,
10 kHz
×
1 counter
•
Pulse plus direction:
100 kHz
×
2 counters
•
Differential phases (4
×
):
50 kHz
×
1 counter, 5 kHz
×
1
counter
N
3
0/40/60 CPU Units:
•
Incremental: 100 kHz
×
3
counters, 10 kHz
×
3
counters
•
Up/down: 100 kHz
×
2 counters
•
Pulse plus direction:
100 kHz
×
2 counters
•
Differential phases (4
×
):
50 kHz
×
2 counters
Section 11
Pulse outputs
Not supported
2 outputs (pulse plus direction
only)
An external power supply is
required for pulse outputs.
N14/20 CPU Units: 2 outputs
(pulse plus direction only)
N
3
0/40/60 CPU Units: 4 outputs
(pulse plus direction only)
An external power supply is
required for pulse outputs for
N
3
0/40/60 CPU Units.
Section 12
PWM outputs
Not supported
1 output
An external power supply is
required for PWM outputs.
1 output
An external power supply is
required for PWM outputs for
N
3
0/40/60 CPU Units.
Section 1
3
Built-in serial communi-
cations
1 port (RS-2
3
2C)
2 ports (RS-2
3
2C+RS-4
8
5)
Not supported
Section 14
Optional serial communi-
cations
Not supported
Not supported
N14/20 CPU Units: 2 ports max.
N
3
0/40/60 CPU Units:
3
ports
max.
(Using Serial Option Board with
2 ports)
Section 14
Section 17
Built-in Ethernet
Not supported
Not supported
N14/20 CPU Unit: 1 port
N
3
0/40/60 CPU Units: 2 ports
(Switch function)
Section 15
PID temperature control
Supported
Supported
Supported
Section 16-1
Clock functions
Not supported
Supported
(While power is supplied)
Supported
(While power is supplied)
Section 16-2
DM backup
Supported
Supported
Supported
Section 16-
3
Security function
Supported
Supported
Supported
Section 16-4
Summary of Contents for SYSMAC CP Series
Page 3: ......
Page 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Page 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Page 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Page 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Page 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Page 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Page 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Page 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Page 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Page 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Page 577: ......