7-5
7 PLC Setup
CP2E CPU Unit Software User’s Manual(W614)
7
-2 PLC
Setup Settings
7
7-2
-4 Ser
ial Option P
or
t 1/Built-in RS-2
3
2C
Po
rt
The settings are applicable to the N
-type CPU Units with Serial Option port 1, and the E/S
-type
CPU units with built-in RS-2
3
2C port.
Since this setting is reflected by power OFF and ON, the PLC Setup and the actual operation settings
may be different. The actual operation settings can be confirmed in words A617.
7-2-4
Serial Option Port 1/Built-in RS-232C Port
Communications Settings
Name
Default
Possible settings
When setting is read by
CPU Unit
1
Communications Settings
Standard (9,600;
1, 7, 2, E)
(Default settings)
Standard
Baud rate: 9,600 bps
Start bits: 1 bit
Data length: 7 bits
Parity: Even
Stop bits: 2 bits
When power is turned ON
Custom
2
Mode
(When custom settings have been selected.)
Host Link
Host Link
When power is turned ON
NT Link (1:N)
RS-2
3
2C (No-protocol)
PC Link (Slave)
PC Link (Master)
Modbus-RTU Easy Master
Modbus-RTU Slave
2-1
Host Link Settings
2-1-1
Baud
9,600 bps
1,200 bps
When power is turned ON
2,400 bps
4,
8
00 bps
9,600 bps
19,200 bps
38
,400 bps
57,600 bps
115,200 bps
2-1-2
Format (data length, stop
bits, parity)
7 bits, 2 bits, even
7 bits, 2 bits, even
When power is turned ON
7 bits, 2 bits, odd
7 bits, 2 bits, no parity
7 bits, 1 bit, even
7 bits, 1 bit, odd
7 bits, 1 bit, no parity
8
bits, 2 bits, even
8
bits, 2 bits, odd
8
bits, 2 bits, no parity
8
bits, 1 bit, even
8
bits, 1 bit, odd
8
bits, 1 bit, no parity
2-1-
3
Unit Number
0
0
When power is turned ON
:
3
1
2-2
NT Link (1:N) Settings
2-2-1
Baud
115,200 bps
38
,400 bps (standard)
When power is turned ON
115,200 bps (high speed)
2-2-2
No.NT/PC Link Max.
(Highest unit number of PT
that can be connected to
the PLC)
1
0
When power is turned ON
:
7
Summary of Contents for SYSMAC CP Series
Page 3: ......
Page 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Page 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Page 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Page 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Page 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Page 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Page 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Page 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Page 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Page 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Page 577: ......