![background image](http://html.mh-extra.com/html/omron/sysmac-cp-series/sysmac-cp-series_user-manual_742262426.webp)
17 Analog Input/Output Option Board
17-20
CP2E CPU Unit Software User’s Manual(W614)
•
To make the connection, press the release button in with a small flat blade screwdriver and push
the line in while the lock is released. Remove the screwdriver and lock it inside.
•
To disconnect the wiring, press the release button in with a small flat blade screwdriver and pull
the line out while the lock is released.
Note 1
Ferrules without plastic sleeve cannot be used.
2
When using stranded wire, twist the core so that the barbed wires cannot protrude.
3
Do not solder-plate the end of cable.
The screwdriver shown below is recommended for wiring.
To prevent noise, 2-core shielded twisted-pair cable should be used.
z
Wiring for Analog Inputs
z
Wiring for Analog Outputs
Note 1
When an input is not being used, short the V IN, I IN and COM terminals.
2
Separate wiring from power lines (AC power supply lines, high-voltage lines, etc.)
3
When there is noise in the power supply line, install a noise filter on the input section and the power supply.
4
When external power is supplied, or when the power is interrupted, there may be a pulse status analog
output of up to 1 ms. If this status is a problem, take the following measures.
•
Turn ON the power to the CP2E N
-type CPU Unit, check the operation status, and then turn ON the
power at the load.
•
Turn OFF the power to the load and then turn OFF the power to the CP2E N
-type CPU Unit.
Model
Manufacturer
SZS 0.4
×
2.5
Phoenix Contact
Wiring for Analog I/O
0.4mm
Side
Front
2.5mm
V I
N
COM
I I
N
V I
N
COM
I I
N
Analog
de
v
ice
w
ith
v
oltage
o
u
tp
u
t
Analog
I/O
Option
Board
+
−
+
−
Analog
de
v
ice
w
ith
c
u
rrent
o
u
tp
u
t
Analog
I/O
Option
Board
2-core shielded
t
w
isted-pair ca
b
le
2-core shielded
t
w
isted-pair ca
b
le
FG
FG
COM
V OUT
Analog
I/O
Option
Board
Analog
de
v
ice
w
ith
v
oltage
inp
u
t
FG
2-core shielded
t
w
isted-pair ca
b
le
+
−
Summary of Contents for SYSMAC CP Series
Page 3: ......
Page 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Page 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Page 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Page 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Page 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Page 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Page 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Page 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Page 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Page 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Page 577: ......