14-29
14 Serial Communications
CP2E CPU Unit Software User’s Manual(W614)
14
-5 Serial PLC
Lin
ks
14
14-5-
3
PLC
Setup
Built-in RS-2
3
2C, Built-in RS-4
8
5 or Serial Port Tab Page
Built-in RS-2
3
2C, Built-in RS-4
8
5 or Serial Port Tab Page
Parameter
Setting
Communications Settings
Set the communications settings to the same values as the connected
PLCs.
If the connected PLCs are set to 115,200 bps, select the
Cu
s
tom
Option,
set the baud rate to 115200. The format can be set to any value.
Mode
Select
PC Link (Ma
s
ter).
Link Words
Set to 10 (default) for the Master only. 10 words (default)
PC Link Mode
Select
All
or
Ma
s
ter.
NT/PC Link Max.
Set the highest unit number of the connected slaves.
Settings at the Polled Unit
Parameter
Setting
Communications Settings
Set the communications settings to the same values as the connected
PLCs.
If the connected PLCs are set to 115,200 bps, select the
Cu
s
tom
Option,
set the baud rate to 115200. The format can be set to any value.
Mode
Select
PC Link (Slave)
.
PC Link Unit No.
Set the unit number (0 to 7).
Summary of Contents for SYSMAC CP Series
Page 3: ......
Page 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Page 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Page 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Page 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Page 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Page 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Page 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Page 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Page 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Page 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Page 577: ......