15 Ethernet
15-8
CP2E CPU Unit Software User’s Manual(W614)
15-2-2 Comparison with Previous Models (Ethernet Related)
Model
CP2E N
-type CPU
Units
CP1W-CIF41
CS1W-ETN21
CJ1W-ETN21
Local IP address
192.16
8
.250.FINS node
address
192.16
8
.250.1
192.16
8
.250.FINS node
address
FINS node address
Set in PLC setup
Set in system settings
Set by rotary switch
Physical layer
100/10Base-TX
(Auto-MDIX)
100/10Base-TX
(Auto-MDIX)
100/10Base-TX
Number of nodes
254
254
254
Data length of FINS message
1004 bytes (Max)
1004 bytes (Max)
2012 bytes (Max)
FINS buffer size
16K bytes
8
K bytes
3
92K bytes
Driver buffer number
Input:
8
×60
8
bytes
Output: 4×1600 bytes
Input: 16×256 bytes
Output:
8
×256 bytes
Input: 50×1.5K bytes
Output: 50×1.5K bytes
Process of driver buffer overflow
The last packet will be
dropped.
The last packet will be
dropped.
The last packet will be
dropped.
Connection number (FINS/TCP)
3
for user
1 for CX-Programmer auto
connection
2 (only server)
16
PLC maintenance via the Internet
Not supported
Not supported
Not supported
Server specification
Specification by IP
address or by host name
(DNS Client Function)
Not supported
Specification by IP address
or by host name
(DNS Client Function)
FINS
comm.
service
Automatic IP address
acquisition
A computer automatically
acquiring IP addresses
can send commands to
the PLC and receive
responses.
A computer automatically
acquiring IP addresses
can send commands to
the PLC and receive
responses.
A computer automatically
acquiring IP addresses can
send commands to the PLC
and receive responses.
FINS communication with
computer without fixed
node address
Possible (with automatic
allocation) (Client FINS
automatic node address
allocation function, TCP/IP
only)
Possible (with automatic
allocation) (Client FINS
automatic node address
allocation function, TCP/IP
only)
Possible (with automatic allo-
cation) (Client FINS auto-
matic node address
allocation function, TCP/IP
only)
Handling TCP/IP
With FINS communica-
tions, both UDP/IP and
TCP/IP (
3
max.) possible.
With FINS communica-
tions, both UDP/IP and
TCP/IP (2 max.) possible.
(Only can be set to server)
With FINS communications,
both UDP/IP and TCP/IP (16
max.) possible.
Simultaneous connection
of multiple applications in
a computer
Possible (with both
UDP/IP and TCP/IP)
Possible (with both
UDP/IP and TCP/IP)
Possible (with both UDP/IP
and TCP/IP)
Mail function
Not supported
Not supported
E-mail attachments with I/O
memory data are possible for
the mail send function.
(SMTP, file attachment) With
the mail receive function,
commands can be received
from the PLC. (POP
3
receive)
FTP server function
Not supported
Not supported
Supported
Socket services function
Supported
Not supported
Supported
Automatic clock information
adjustment
Supported
Not supported
Supported
IP conflict (GARP)
Supported
Not supported
Supported
TCP keep-alive function
Supported
Not supported
Supported
Multicast function
Not supported
Not supported
Not supported
Web function
Not supported
Supported
Supported
Switch function
Supported
Not supported
Not Supported
Summary of Contents for SYSMAC CP Series
Page 3: ......
Page 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Page 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Page 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Page 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Page 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Page 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Page 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Page 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Page 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Page 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Page 577: ......