107
8-1-3 Send/Receive Data Areas
The data areas that can be transferred using the SEND(90) and RECV(98)
instructions differs according to the PC model being used. Check the operation
manual for your PC for details.
Send/Receive Data Areas
When remote node is C-series PC
When remote node is CV-series PC
Area
Area
type
Word addresses
Area
Area
type
Word addresses
IR and SR areas
00
0 to 511
CIO Area
00
0 to 2555
LR area (LR)
06
0 to 63
CPU Bus Link Area (G)
01
0 to 255
HR area (HR)
07
0 to 99
Auxiliary Area (A)
02
0 to 511
AR area (AR)
08
0 to 27
Timer Area (TIM)
03
0 to 1023
Timer/Counter Area
(TIM/CNT)
03
0 to 511
Counter Area (CNT)
04
0 to 1023
DM Area (DM)
05
0 to 9999
DM Area (DM)
05
0 to 24575
Expansion DM
Banks 0 to 7:
Current bank:
10 to 17
18
0 to 6143
Expansion DM
Banks 0 to 7:
Current bank:
10 to 17
18
0 to 32765
Word
Bits 15 to 08
Bits 07 to 04
Bits 03 to 00
D
Area code
0
Word address
(D+1)
Word address
Word address
Word address
Specified in binary coded decimal (BCD)
Set the send/receive area within the above ranges.
A data length of 1,000 words is valid only when the remote node supports it. If the
remote node can only return 256 words, any data greater than 257 words is not
guaranteed.
The PC Card Unit supports a data length of 1 to 997 words for the SEND(90)
instruction, and a data length of 1 to 1,000 words for the RECV(98) instruction.
8-1-4 Instruction Status
Status information for executed SEND(90), RECV(98), and CMCR instructions
is reflected in the SR Area of the PC as instruction execution flags and instruc-
tion response codes.
The following two instruction execution flags are used:
Instruction Enabled Flag:
ON (“1”) when the SEND(90), RECV(98), or CMCR instruction can be executed.
Instruction Error Flag:
ON (“1”) when the SEND(90), RECV(98), or CMCR instruction has terminated
abnormally.
If multiple instructions are to be used, always make sure that the Instruction
Enabled Flag is ON before executing the next instruction (i.e., perform exclusive
control).
Indirect Addressing:
Operand 2 (D) Data When
Bit 12 of Word (C+1) = 1
Structure of Instruction
Execution Flags
Outline
Section 8-1
Summary of Contents for SYSMAC C200HW-PCS01-EV1
Page 1: ...Cat No W313 E1 3 PC Card Unit SYSMAC C200HW PCU01 C200HW PCS01 EV1 OPERATION MANUAL...
Page 2: ......
Page 3: ...SYSMAC C200HW PCU01 C200HW PCS01 EV1 PC Card Unit Operation Manual Revised January 2000...
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 18: ......
Page 34: ......
Page 38: ......
Page 60: ......
Page 80: ......
Page 82: ......
Page 88: ......
Page 120: ......
Page 148: ......
Page 178: ......
Page 214: ......
Page 220: ......
Page 232: ......
Page 234: ......
Page 236: ......
Page 238: ......
Page 240: ......