21
Unit Restrictions and Mounting Locations
When a PC Card Unit is used, only one SYSMAC LINK Unit (or SYSMAC
NET Link Unit) can be used on the CPU Backplane.
When a PC Card Unit and SYSMAC LINK Unit (or SYSMAC NET Link Unit)
are used together on the CPU Backplane, they must be mounted in the slots
shown in the following illustration.
PC Card Unit
SYSMAC LINK Unit
Mount the PC Card Unit to the
left of the SYSMAC LINK Unit
C200HX/HG/HE CPU
The previous Bus Connection Units (C200HW-CE001/002) cannot be used
with the PC Card Unit. Likewise, the PC Card Unit’s Bus Connection Units
(C200HW-CE011/012) cannot be used with other Units, except that the
C200HW-CE012 can be used to also connect a SYSMAC LINK or SYSMAC
NET Link Unit.
4. Programming
Use SYSMAC Support Software to create the ladder program. For details
regarding ladder programming, refer to the SYSMAC Support Software
Operation Manuals.
5. Debugging
Use a memory card with the program that has been created and correct any
bugs that may be found.
6. Operation
Proceed with actual operation.
5-1 to 5-5
5-6
Procedures
Section 3-2
Summary of Contents for SYSMAC C200HW-PCS01-EV1
Page 1: ...Cat No W313 E1 3 PC Card Unit SYSMAC C200HW PCU01 C200HW PCS01 EV1 OPERATION MANUAL...
Page 2: ......
Page 3: ...SYSMAC C200HW PCU01 C200HW PCS01 EV1 PC Card Unit Operation Manual Revised January 2000...
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 18: ......
Page 34: ......
Page 38: ......
Page 60: ......
Page 80: ......
Page 82: ......
Page 88: ......
Page 120: ......
Page 148: ......
Page 178: ......
Page 214: ......
Page 220: ......
Page 232: ......
Page 234: ......
Page 236: ......
Page 238: ......
Page 240: ......