215
Appendix E
FINS Response Codes from the PC Card Unit
When an error occurs in a FINS command sent to a PC Card Unit, an error response code is returned. Although
there are other response codes that are given only for certain commands, the following is a list of response codes
common to all commands.
Response code
Cause
0103
Transmission buffer full; transmission not possible.
0201
Destination IP address not recognized; transmission not
possible.
0202
Specified Unit nonexistent; transmission not possible.
0301
Network error; transmission not possible.
0401
Command frame not supported (MRC, SRC).
0401
Unsupported FINS frame (Protocol) received.
0501
Routing table setting error; transmission not possible.
0502
Routing table nonexistent; transmission not possible.
0503
Routing table error; transmission not possible.
1005
FINS frame with an incorrect destination received.
1001
Transmission size exceeds 1472 bytes.
2305
IP address cannot be converted; transmission not possible.
Summary of Contents for SYSMAC C200HW-PCS01-EV1
Page 1: ...Cat No W313 E1 3 PC Card Unit SYSMAC C200HW PCU01 C200HW PCS01 EV1 OPERATION MANUAL...
Page 2: ......
Page 3: ...SYSMAC C200HW PCU01 C200HW PCS01 EV1 PC Card Unit Operation Manual Revised January 2000...
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 18: ......
Page 34: ......
Page 38: ......
Page 60: ......
Page 80: ......
Page 82: ......
Page 88: ......
Page 120: ......
Page 148: ......
Page 178: ......
Page 214: ......
Page 220: ......
Page 232: ......
Page 234: ......
Page 236: ......
Page 238: ......
Page 240: ......