![background image](http://html.mh-extra.com/html/omron/nt11s/nt11s_operation-manual_744536141.webp)
125
NT11S Status Control
Section 5-4
Example use of the PT status control bits
The example below shows how the PT status control bits are used to execute daily
report printing.
S
Setting at the support tool
Perform the following setting with the support tool.
PT status control area allocated word: CH0100
S
PC program
Create the following PC ladder program:
@ORW(35)
120
#0010
00110
00111
@ANDW(34)
120
#FFEF
(1)
PT status control word
Set the daily report printing bit only to “1”.
PT status control word
(2)
PT status control word
Set the daily report printing bit only to “0”.
PT status control word
120
120
S
Program operation
(1) When contact 00110 comes ON, the daily report printing bit (bit 4) of the PT
status control area is set to “1”. The status of bits other than bit 4 remains un-
changed.
When bit 4 is set to “1”, the daily report is printed.
(2) When contact 00111 comes ON, the daily report printing bit (bit 4) of the PT
status control area is set to “0”. The status of bits other than bit 4 remains un-
changed.