Connection to a PC by the Host Link (RS-232C Type)
Section 2-4
Connecting to a Host Link Unit
S
C200H rack-mounting type: C200H-LK201(--V1)
[Setting the front switches]
Set each switch with a flat blade screwdriver so that the values or symbols in the
setting value window agree with the following.
S
Unit No. (SW1, SW2)
Set these switches to “0”.
S
Instruction level, parity, and transfer code (SW4)
Set this switch to “2”.
S
Baud rate (SW3)
Set this switch to “5” to select 9600 bps.
Set this switch to “6” to select 19200 bps.
5
2
[Setting the rear switches]
S
1-to-1/1-to-N selection (DIP switch)
Set No.3 to “ON”.
S
CTS selection (selector switch)
Set this always to “0V” (ON).
CTS
selector
switch
External
0V (ON)