Caution
100
Outline of Host Link / NT Link Operation
Section 5-1
As the number of the numeral table is written, the PT status numeral setting
strobe flag is simultaneously set ON (1). After this is notified to the PC, this flag
reverts to OFF (0). Checking the status of this flag will provide a simple method
of checking if a number has been input from the NT11S.
Note that this function is not available with the character-string memory table.
S
PT status (refer to page 126)
The NT11S operation status and other information are written with the ON or
OFF of the bits as shown below.
Screen switching strobe
Password input error flag
15 14 13 12 11 10 9
8 Bit
PT status notify bits
0
0
0
0
m+2CH
PT operation status (1 (ON): RUN / 0 (OFF): STOP)
Numeral setting strobe flag
The PT status control area (PC to PT) can be allocated to the following PC areas.
Symbol
Area Name
Allocated
DM
Data Memory
f
CH
Internal/Special Relay
f
TIM
Timer
×
CNT
Counter
×
HR
Holding Relay
f
AR
Auxiliary Relay
f
LR
Link Relay
f
f
: OK
×
: NG
Set so that there is no overlap between the PT status control area and PT status
notify area. Otherwise the system may operate unpredictably.