73
CX-Programmer Procedures
Section 4-12
6.
Set the settings for node 2 and 3 in the same way. The following example
shows the settings for node 2.
The following example shows the settings for node 3.
Node address
Local node address: 1
Common link
parameters
CIO Area size CIO Area local node send size: 20 words.
DM Area size DM Area local node send size: 30 words.
Refresh
parameters
PLC type
Select “CV/CVM1”
Start
word
CIO
CIO Area local node data link start address:
CIO 1000.
DM
DM Area local node data link start address: D00500
Refresh
nodes
Node refresh order: 1, 3, 2
Node addresses are listed in order with the starting
node address first. Because here the local node is
listed first, node 1 will first send data and then
received data in order from nodes 3 and then 2.