Data Link Table Example
Section 4-7
Example of Node 2 Settings
Node 2 Table
Note
When setting data link tables for CS-series SYSMAC LINK Units with CX-Pro-
grammer Ver. 1.2 (Service Pack 1), set the PLC type to CV/CVM1. With CX-
Programmer Ver. 2.0 or later, it is possible to set a CS-series PLC type.
Setting Tables for Other Nodes
Node 5 Table
Item
Setting
Node address
Local node address: 2
Common link
parameters
Number of words in
CIO Area
CIO Area local node send size: 10 words
Number of words in
DM Area
DM Area local node send size: 10 words
Refresh param-
eters
PLC type
Select “CV/CVM1”
Start word
CIO
CIO Area local node data link start address:
CIO 1000
DM
DM Area local node data link start address:
D00000
Refresh nodes
Node refresh order: 2, 5, 6, 8
Node addresses are listed in order with the
starting node address first. Because here
the local node is listed first, node 2 will first
send data and then received data in order
from nodes 5, 6, and 8.
Item
Setting
Node address
Local node address: 5
Common link
parameters
Number of words in
CIO Area
CIO Area local node send size: 15 words
Number of words in
DM Area
DM Area local node send size: 10 words
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...