102
PLC Network Instructions
Section 6-2
Unit Address has been set to FE, commands will be sent to the SYSMAC
LINK Unit, Controller Link Unit, or Ethernet Unit with the relevant destina-
tion node address.
6.
Response Bit
Usually set this bit to OFF (0: required). If no response is required, set the
bit to ON (1: Not required).
7.
Communications Port Number
Set the communications port number that the CMND(490) instruction will
be sent to.
8.
Number of Retries
Set the number of retries for unsuccessful transmissions. You can set the
number between 1 to 15. If 15 has been set, for example, the CMND(490)
instructions will be re-transmitted up to 15 times when the PLC does not
receive a response from the destination node.
9.
Response Monitor Time (Unit: 0.1 S)
Designates the length of time that the PLC retries transmission when bit
15 of C+3 is OFF and no response is received. The default value is $0000,
which indicates 2 seconds.
Note
If more than the
Number of Bytes to Receive
is received, no response will be
stored. If fewer bytes are received, the response data will be stored and the
unused memory area of the PLC will remain unchanged.
Range of Control Data
The permissible ranges of control data are as follows:
Note
(1) FE, or unit 10 (FE can be set when the destination is a SYS-
MAC NET Link, SYSMAC LINK Unit, Controller Link Unit, or Ethernet
Unit.
Destination
Address (hexadecimal)
PLC (CPU)
00
NSB (computer)
01 (user application)
CPU Bus Unit
10 to 1F: Unit Number 0 to F (0 to15)
Inner Board
E1
Unit connected with the network
FE
Item
Value
Number of bytes to send
0002 to 021E (2 to 542 bytes)
Number of bytes to receive
0002 to 021E (2 to 542 bytes)
Destination network address
00:
Local network
01 to 7F: Destination network address
Destination node address
00:
Transmission within local PLC
01 to 3E: Destination node address (1 to 62) (SYSMAC LINK)
01 to 20: Destination node address (1 to 32) (Controller Link)
01 to 7E: Destination node address (1 to 126) (Ethernet, SYSMAC NET)
FF:
Broadcasting
Destination unit address
00:
PLC (CPU Unit)
01:
Computer (NSB), user application 1
10 to 1F,
or FE:
CPU Bus Unit (see note 1).
E1:
Inner board
FE:
SYSMAC NET Link Unit or SYSMAC LINK Unit
Response Bit
0 (OFF):
Required
1 (ON):
Not required
Communications port number
0 to 7 (0 to 7)
Number of retries
0 to F (0 to 15)
Response monitor time
0000:
2 s (default)
0001 to FFFF: 0.1 to 6,553.5 s with 0.1-s increments (set by the user)
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...