30
Cable Connections
Section 2-4
Note
(1) A label has been placed over the upper surface of the SYSMAC LINK Unit
to prevent wire cuttings from entering the Unit. When wiring the backup
power supply, leave the label in place.
(2) When wiring is complete, remove the label to avoid overheating.
(3) Use a power supply that is not connected to PLC operation, as in the case
of the node bypass function, for the backup power supply so that when
the power to the PLC is turned OFF, the backup power supply will contin-
ue.
(4) Use a dedicated power supply for the backup power supply. Do not share
a power supply being used for I/O, motors, or control systems.
(5) When two or more nodes are connected to a single backup power supply,
wire each node separately.
Note
Unlike the CV500-SLK11, the CS1W-SLK11 does not require an Auxiliary
Power Supply Unit for the node bypass function. Instead, directly connect a
24-VDC external power source as a backup power supply.
Attach crimp terminals to the power supply cable when connecting the backup
power supply to the SYSMAC LINK Unit.
Crimp Terminals
Use an M3 crimp terminal, as illustrated below.
Current consumption
200 mA max. at 24 V DC (per node)
Inrush current
2.5 A max. (24 V DC, 5-ms rise time)
Item
Specification
Backup power
supply
Backup power
supply
OK
Wrong
Backup
power
supply
24 VDC
6.2 mm max.
6.2 mm max.
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...