31
Cable Connections
Section 2-4
Recommended Crimp Terminals
Note
(1) Always turn OFF the power to the PLC and the backup power supply be-
fore connecting the backup power supply cables.
(2) Separate the backup power supply wires from other power lines and high-
voltage lines to prevent noise.
(3) Always use a crimp terminal for wiring. Do not connect a wire that has
only been twisted directly to a terminal block.
(4) In the interests of safety, it is recommended that round crimp terminals
are used.
(5) When mounting the crimp terminal, always use the appropriate tools for
each crimp terminal and follow the appropriate installation procedures.
Contact the crimp terminal manufacturer for details on the appropriate
tools and procedures. Failure to use the appropriate tools and procedures
could cause cables to break.
(6) Measure the length of peeled cable during installation according to the
crimp terminal used and make sure that the peeled length is not too long.
Cover the compressed section of the crimp terminal and cable with vinyl
tape or heat-shrinking tube.
(7) Be sure not to reverse the power supply polarity.
(8) Tighten the screws on the terminal block firmly. The correct tightening
torque is 0.5 N
•
m. If the screws are too loose, short-circuit, malfunction
or burning may result.
(9) Do not pull backup power supply cables with excessive force.
(10) Do not bend backup power supply cables.
(11) Do not place any object on top of backup power supply cables.
(12) Supply power only after checking the wiring thoroughly.
Manufacturer
Model
Remarks
Suitable wiring
range
Japan Crimp Termi-
nals KK
V1.25-N3A
Vinyl insulated
forked terminal
0.25 to 1.65 mm
2
(AWG #22 to #16)
V1.25-MS3
Vinyl insulated
round terminal
MOLEX JAPAN
CO., LTD.
VSY1.25-3.5L
Vinyl insulated
forked terminal
0.3 to 1.65 mm
2
(AWG #22 to #15)
RAV1.25-M3
Vinyl insulated
round terminal
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...