128
Troubleshooting
Section 8-1
8-1
Troubleshooting
This section explains errors that may occur and how to solve them.
8-1-1
Error Indications
You can check possible system errors using the indicators on the front panel
of the SYSMAC LINK Unit. The tables below list error conditions, their proba-
ble cause, and possible remedies.
RUN, ERC, ERH, and INS Indicators
Indicators
CPU Bus Unit CIO
Area error
information
Error
log
Probable cause
Remedy
RUN
ERC
ERH
INS
Lit
Not lit
Not lit
Lit
---
---
Unit is participating in
network normally.
---
Not lit
Not lit
Not lit
Not lit
---
---
Power to PLC is
turned OFF.
Check the voltage, and check
that power is being supplied
normally.
---
---
SYSMAC LINK Unit
mounting is loose.
Firmly fix the SYSMAC LINK
Unit to the Backplane.
---
---
SYSMAC LINK Unit
mounting position is
incorrect.
Refer to
2-3 Mounting to
Backplanes
, then mount the
Unit correctly.
---
---
SYSMAC LINK Unit is
faulty.
Replace the SYSMAC LINK
Unit if the indicators fail to
light even when mounted to
another PLC.
Not lit
Lit
Not lit
Not lit
---
---
SYSMAC LINK Unit is
broken.
Replace the SYSMAC LINK
Unit if the ERC indicator fails
to light even when mounted
to another PLC.
Both bit 08 (node
address setting error)
and bit 15 (error log
information) are ON.
0214
Hex
Node address setting
is out of range.
Correct the node addresses
to within the range of 1 to 62,
then turn ON the power
again.
---
Lit
Not lit
Not lit
Both bit 01 (data link
table error) and bit 15
(error log informa-
tion) are ON.
0210
Hex
Communications con-
troller error.
Replace the SYSMAC LINK
Unit.
Lit
Lit
---
Not lit
Both bit 09 (duplicate
node address setting
error) and bit 15 (error
log information) are
ON.
0211
Hex
Table contains dupli-
cate node addresses.
Change the settings so that
there are no duplicate node
addresses in the same net-
work, then turn ON the power
again.
Wrong connection to
network (optical fiber
only).
Check the network, and
reconnect the cables cor-
rectly.
Not lit
Not lit
Lit
Not lit
---
---
The I/O table in the
CPU Unit has not
been created, or con-
tains an error.
Set the I/O table correctly.
---
---
Table contains dupli-
cate unit numbers.
Change the settings so that
there are no duplicate unit
numbers at the same PLC
(including any on CS-series
Expansion Racks), then turn
ON the power again.
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...