22
Cable Connections
Section 2-4
1,2,3...
1.
Cut the cable to the required length.
2.
Remove 15 mm of the outer covering. Be careful not to damage or to dis-
tort the braiding.
3.
Insert the ferrule as shown below.
4.
Spread the tip of the braiding, and insert the sleeve. Using the trimming
tool, push in the sleeve flange forcefully until it fits flush with the braiding.
5.
Align A of the central conductor polyethylene projecting towards the out-
side of the trimming tool with the outside of the tool as shown below and
then cut the polyethylene.
LA mm = L mm
−
12 mm
Approx. 24.5 mm
Approx. 24.5 mm
L
LA
Cable
(Unit: mm)
15 mm
Ferrule
Cable
Ferrule
Sleeve
Ferrule
Shield
Sleeve
B
C
Trimming tool
Blade
Ferrule
Conductor
A
Shield
Sleeve