86
Routing Tables
Section 5-2
5-2
Routing Tables
Routing tables are required for data exchange with other networks or when
more than one SYSMAC LINK Unit, Controller Link Unit, or Ethernet Unit is
mounted on the PLC. For data exchange with other networks, set a routing
table on the local node, destination node, and relay node from a host com-
puter or the Support Software. Refer to the Support Software manuals for
details.
!Caution
The CPU Bus Units will be reset if the routing tables are transferred to the
CPU Unit from a Programming Device. The reset is required to update the
routing table settings. Confirm that the controlled system will not be adversely
affected before transferring the routing tables.
5-2-1
Routing Table Configuration
The routing tables consist of a local network table and relay network table and
determine the communications path for data exchange between networks.
5-2-2
Local Network Table
If more than one Communications Unit (SYSMAC LINK, Controller Link, or
Ethernet Unit) is mounted on the PLC, a local network table is required. The
local network table has a list of each network and its corresponding Unit.
Two data items are set for each Unit:
Local Network Address:
Network address of the Unit (1 to 127)
CPU Bus Unit Number:
Unit number (0 to 15) of the Communications Unit
5-2-3
Relay Network Tables
To exchange data between two networks, you must set up relay network
tables that specify the transmission path to remote destinations.
Data transmission paths include the following settings.
CX-Net Settings Window
Example
Create the routing tables using CX-Net in CX-Programmer as shown below.
Here, the procedure for CX-Net in CX-Programmer Ver. 1.2 (Service Pack 1)
is given as an example.
• Local Network Table
Local network address is 10 and the SYSMAC LINK Unit’s unit number is
5.
• Relay Network Table
Destination network address is 20, relay network address is 10, and relay
node address is four.
Routing tables
Local network table
Relay network table
Item
Range
Contents
Destination net-
work
1 to 127
The network address of the desig-
nated node.
Relay network
1 to 127
The address of the network through
which the destination network can be
reached.
Relay node
1 to 62 for SYSMAC LINK
1 to 32 for Controller Link
1 to 126 for Ethernet
The address of the node on the relay
network through which the destina-
tion network can be reached.
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...