72
CX-Programmer Procedures
Section 4-12
5.
Enter the value in each field.
The following example shows settings for node 1.
Set the local node CIO Area send size in
words. Setting range: 0 to 254 words.
When this setting is 0, the local node will
not send CIO data (i.e., will receive only).
Set the local node DM Area send
size in words. Settings range: 0 to
254 words. When this setting is 0,
the local node will not send DM
data (i.e., will receive only).
The node address selected for editing
Set in order the node addresses with which the local node will refresh data, starting
with the data link start addresses set above. If the address of the local node is set,
it will send the specified word data to other nodes. If the address of another node is
set, the local node will receive the data sent by that node. For example, if you enter
3, 2, 1 as the refresh order, the node addresses will be allocated in the order 3, 2,
1, starting from the start address. If the local node address is 1, it will receive data
from node 3, then from node 2, and finally, it will send data itself). Always include
the local node in the refresh node order. Data will not be received from the local
node by another other node if the local node is not specified.
If using CX-Programmer Ver. 1.2
(Service Pack 1), select CV/CVM1
for the PLC type when using a CS-
series SYSMAC LINK Unit. The
words for manual settings will be
limited to the same words as for
CVM1 and CV-series PLCs.
If using CX-Programmer Ver. 2.0 or
later, CS-series PLC types can be
specified and so the above
limitations to words for manual
settings do not apply.
Set the address of the first
word in the CIO Area data link
of the local node. Setting
range: CIO 0000 to CIO 2555.
Set the address of the first word
in the DM Area data link of the
local node. Setting range:
D00000 to D24575. (Setting
range with CX-Programmer Ver.
2.0 or later: D00000 to D32767.)
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...