111
FINS Command/Response Format
Section 6-3
6-3-5
FINS Commands for SYSMAC LINK Units
Note
These commands can also be sent to the PLC.
6-3-6
Response Codes
A response code consists of two bytes. If a command is completed normally, a
response code of 00 00 will be returned. The first two digits of a response
code are called the main response code (MRES) and the last two digits are
called the sub-response code (SRES). If command execution results in an
error, one of the response codes listed in the following table will be returned.
Refer to
8-1-2 Probable Causes and Remedies of Response Code Errors
for
details.
Command
code
Name
Page
04
01
DATA LINK START (see note)
112
02
DATA LINK HALT (see note)
112
03
RESET
112
05
01
CONTROLLER DATA READ (see note)
113
06
01
CONTROLLER STATUS READ (see note)
113
02
NETWORK STATUS READ
115
03
DATA LINK STATUS READ
117
08
01
INTERNODE ECHO TEST
118
02
BROADCAST TEST RESULTS READ
119
03
BROADCAST TEST DATA SEND
119
21
02
ERROR LOG READ (see note)
120
03
ERROR LOG CLEAR (see note)
121
MRES
Description
00
Normal completion
01
Local node error
02
Destination node error
03
Controller error
04
Not executable
05
Routing error
10
Command format error
11
Parameter error
20
Read not possible
21
Write not possible
22
Not executable in current PLC mode
23
No Unit
24
Start/Stop not possible
25
Unit error
26
Command error
30
Access right error
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...