150
Periodic Inspections
Section 10-1
10-1 Periodic Inspections
SYSMAC LINK Units must be inspected on a regular basis to ensure correct
operation. SYSMAC LINK Units are built primarily of solid-state components
and contain almost no parts subject to wear. Nevertheless, the life span of
some solid-state components can be shortened as a result of adverse envi-
ronmental conditions.
We recommend that the following points be checked at least once every 6 to
12 months as part of a standard inspection program. Ambient conditions
should be checked more frequently. If any of these items deviate from the pre-
scribed standards, take appropriate action to correct the condition.
We recommend that users have backup Units available to make repairs and
minimize down-time if a problem occurs in a SYSMAC LINK Unit.
10-2 Handling Precautions
Please observe the following precautions in the event of a problem:
• Always turn OFF the power when replacing a SYSMAC LINK Unit.
• If a SYSMAC LINK Unit fails, replace it with a new one and immediately
verify that the new Unit is working properly.
• When returning a malfunctioning SYSMAC LINK Unit for repair, please
attach a detailed description of the problem to the Unit and return it to the
sales office nearest you (see listing at the end of this manual).
• If you suspect that a poor connection is the cause of a malfunction, clean
the connectors using a clean, soft cloth and industrial-grade alcohol.
Remove any lint or threads left from the cloth, and re-mount the SYSMAC
LINK Unit.
10-3 Tools and Equipment Needed for Inspection
The following tools and equipment will be needed to perform inspection and
adjustments.
• Assorted flat-blade and Phillips screwdrivers
• Circuit tester or digital voltmeter
• Industrial-grade alcohol and clean cotton cloth
• Synchroscope
• Pen-chart recording oscilloscope
• Thermometer, hygrometer
Inspection item
Inspection contents
Standard operation
Inspection method
Environmental conditions
Check the ambient tempera-
ture and the temperature
inside the unit.
0 to 55
°
C
Thermometer
Check the ambient humidity
and the humidity inside the
unit.
10 to 90% (Check there is no
condensation.)
Hygrometer
Check there is no dust.
Clean away any dust.
Eyesight
Mounting conditions
Check the SYSMAC LINK
Unit is firmly fixed.
Tighten any loose Units.
Eyesight
Check the cable connectors
have been fully inserted.
Tighten any loose cables.
Eyesight
Check that external wiring
screws are not loose.
Tighten any loose screws.
Phillips screwdriver
Check that external wiring
cables are not frayed.
Inspect the wiring externally
for any abnormalities.
Eyesight
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...