104
PLC Network Instructions
Section 6-2
6-2-8
Program Example
0000
00
A202
07
1200
02H
1200
01
1210
00
1200
00
A219
07
0000
01
A219
07
1200
00
1200
03
1200
02
A202
07
1200
00
1210
01
1200
02
A202
07
1200
02
A219
07
1200
02
1200
03
A219
07
1200
00
(011)
KEEP
120000
(021)
@MOV
#000A D00000
(021)
@MOV
#0002
D00001
(021)
@MOV
#0400
D00002
(021)
@MOV
#0705
D00003
(021)
@MOV
#0064
D00004
(070)
@XFER
&0010
0000 D00010
(090)
@SEND D00010
D00020 D00000
(013)
DIFU
120001
(011)
KEEP 120002
(021)
@MOV
#0010 D00005
(021)
@MOV
#0003 D00006
(021)
@MOV
#3000 D00007
(021)
@MOV
#070F D00008
(021)
@MOV
#0000 D00009
(98)
@RECV
A100
2000
D00005
(013)
DIFU
120003
(070)
@XFER &0016
2000
D00040
The SEND(90) program section will run when
CIO 000000 is ON, provided that the Enabled Flag for
port 7 is ON and the RECV(98) instruction has not been
executed.
CIO 120000 is ON while the SEND(90) instruction is
being executed, and it goes OFF when the execution of
the instruction has been completed.
The 10-word data starting from D00010 on the local PLC
is sent to D00020 and following words on the PLC with a
unit address of 0, node address of 4, and network
address of 2.
Word
Content
Meaning
D00000 00
0A Number of words: 10
D00001 00
02 Destination network address: 2
D00002 04
00 Destination node address: 4
Destination unit address: 0
D00003 07
05 Communications port No.: 7
Number of retries: 5
D00004 00
64 Response monitor time: 10 s
Storing the Send Data
The 10-word data starting from 0000 is stored in
D00010 and following words.
Transmission error display
The RECV(98) program will run when CIO 000001 is
ON, provided that the Enabled Flag for port 7 is ON and
the SEND(90) instruction has not been executed.
CIO 120002 is ON while the RECV(98) instruction is
being executed, and it goes OFF when the execution of
the instruction has been completed.
The 16-word data starting from A100 on the PLC with a
unit address of 0, node address of 48, network address
of 3 is stored at CIO 2000 and following words a the
local PLC.
Word
Content
Meaning
D00005 00
10
Number of words: 16
D00006 00
03
Destination network address: 3
D00007 30
00
Destination node address: 48
Destination Unit address: 0
D00008 07
0F
Communications port No.: 7
Number of retries: 15
D00009 00
00
Response monitor time: Default
Reception error display
Reception data processing
When the data is received without an error, the 16-word
data received at CIO 2000 and following words is
stored in D00040 and following words on the same PLC.
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...