93
PLC Network Instructions
Section 6-2
Broadcasting Data
It is possible to transfer the same data to all nodes in a network simulta-
neously by designating the destination node as FF Hex. This transmission is
called broadcasting. No responses are returned to broadcasts.
6-2-2
Communications Specifications
The basic specifications of the network instructions are given in the following
table.
6-2-3
PLC Memory Areas
The memory areas that can be used for data transfer depend on the model of
PLC, as shown in the following table. Be sure not to exceed the end of a mem-
ory area when sending or receiving data. Also be sure to set the operands so
that the end of the data area is not exceeded.
Note
(1) Writing is not possible to words A000 through A447 in the Auxiliary Area.
(2) A maximum of thirteen banks can be used for Expansion DM. For details
on the EM Area and the number of banks, refer to the operation manual
for the PLC model that is being used.
Broadcast data
Node 1
Node 2
Node 3
Node 4
Node 5
Transmission
format
1:1 (SEND(90), RECV(98), or CMND(490))
1:N (SEND(90) or CMND(490); data broadcast, no response.
Max. number of words: 126 with Ethernet, 62 with SYSMAC
LINK, and 32 with Controller Link)
Packet length
SEND(90)/RECV(98): 256 words (512 bytes) max.
CMND(490): 542 bytes max.
Data content
SEND(90): Command/response data for data transmission
RECV(98): Command/response data for data reception
CMND(490):Command/response data for supported functions
Communica-
tions ports
Ports 0 to 7
(8 ports can be used at the same time for data exchange)
Response time-
out time
0000: 2 s
0001 to FFFF:
User settings (in increments of 0.1 s, 0.1 to 6553.5 s)
Number of
retries
0 to 15
Area
Range
CIO
CIO 0000 to CIO 6143
Work Area
W000 to W511
Holding Area
H000 to H511
Auxiliary Area
A000 to A959 (See note 1.)
Timer
T0000 to T4095
Counter
C0000 to C4095
Data Memory
D00000 to D32767
Expansion Data Memory
E00000 to E32767 (See note 2.)
Summary of Contents for CS1W-SLK11-21 - 06-2004
Page 1: ...Cat No W367 E1 02 SYSMAC CS1W SLK11 21 SYSMAC LINK Units...
Page 2: ...CS1W SLK11 21 SYSMAC LINK Units Operation Manual Revised June 2004...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ......
Page 11: ......
Page 17: ......
Page 49: ......
Page 107: ......
Page 139: ...122 FINS Commands for SYSMAC LINK Units Section 6 4...
Page 143: ......
Page 170: ...153 Appendix B Dimensions CS1W SLK11 Optical SYSMAC LINK Unit Unit mm...
Page 171: ...154 Dimensions Appendix B CS1W SLK21 Coaxial SYSMAC LINK Unit Unit mm...
Page 177: ......
Page 179: ......
Page 195: ......
Page 199: ......
Page 202: ...SYSMAC CS1W SLK11 21 SYSMAC LINK Units Cat No W367 E1 02 OPERATION MANUAL...